6 Heat recovery section, plate
6.1 Operating conditions
•
The operating temperature range is -40 °C ... +40 °C.
•
The maximum permissible pressure difference between supply and exhaust air is 800 Pa.
6.2 Safety
WARNING
Observe general and section-specific safety instructions
6.3 Installing
CAUTION
To prevent the risk of freezing, we recommend the use of fresh-air preheating in connection
with a plate heat recovery especially in sites where the exhaust air is humid.
6.4 Commissioning and maintenance
The maintenance interval is 6 months. It is advisable to have the unit serviced at the beginning (autumn) and
at the end (spring) of the heating season.
•
Make sure that the heat transfer surfaces are clean and intact.
•
Check the operation of the dampers. If necessary, lubricate with a silicone-based lubricant.
•
Check the turning direction of the actuator. If necessary, change the direction by turning the switch
on top of the actuator with a flathead screwdriver of suitable size.
•
Clean the heat recovery cube gently with a brush, compressed air or a vacuum cleaner.
•
Check and, if necessary, clean the condensation water discharge system, i.e., drip tray, piping and
water trap.
•
Flush the piping.
•
Make sure that there are no loose components, debris etc., that could get into the fan impeller.
•
Make sure that the electrical cables are intact.
•
Make sure that the access door gaskets and plate heat exchanger are in place and intact. Close the
access door and make sure that every latch tightens properly.