Error Messages
Certain entries or attempted entries may cause the controller to display an error message. Some of the error messages shown
here are also shown as part of the section titled: System Fault Warning Lamp with Digital Displays and the section titled: System
Fault Shutdown Lamp with Digital Displays.
Cannot Calibrate
appears when attempting to calibrate the voltage and current values in the GenSet Calibration menu with the
unit stopped. The unit must be running in order to make adjustments.
Cannot Edit When Stopped
appears in the Voltage Regulator menu when attempting to change the VR Volt Adj value when
the unit is not running.
Default Parameters Loaded.
The fault lamp illuminates yellow and the alarm horn sounds when the controller detects that the
default parameter settings were loaded using SiteTech™ software. The local display shows
Default Pars Warning
.
ECM Address Conflict.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the controller
detects an error with the ECM address. The local display shows
ECMAddr Err Shutdwn
.
ECM Model Mismatch.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the controller
detects an error with the ECM model. The local display shows
ECM Mismatch Shutdwn
.
File System Error.
The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the internal controller
diagnostics detect a firmware file error. The local display shows
File Error Shutdwn
.
Max Alternator Current Low.
The current value listed in the maximum alternator current personality parameter is too low
compared to the kW setting within the personality.
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......