3 Configuring the switching outputs
1
8
3.2 N/O output with configurable hysteresis
Applications
■
Dry run protection
■
Empty signal
Configuration
■
Configure the
Qx
switching output as normally open
○
Set the parameter in the
QxMENU-OUx
menu to
Qx_Hno
■
Set the switching point
○
Set the value in the
QxMENU-SPx
menu to level in mm (e.g., 500 mm)
■
Set the reset point
○
Set the value in the
QxMENU-RPx
menu to level in mm (e.g., 450 mm)
■
Select the electrical property [NPN/PNP/DRV (push/pull)]
○
Select the parameter in the
QxMENU-TYPx
menu
○
The following information applies:
▫
Qx-PNP = Switching output in PNP circuit
▫
Qx-NPN = Switching output in NPN circuit
▫
Qx-Drv = Switching output in push/pull function
■
Switching output behavior
Level
t
SP
RP
active
inactive
Error signal
Switching output
PNP
NPN
DRV
Error status
Normally open/HNO
active
Uv
0 V
Uv (PNP switched)
inactive
inactive
0 V
1)
Uv
2)
0 V (NPN switched)
1)
Pulldown only
2)
Pullup only