![Knick Stratos Pro A401B PH User Manual Download Page 106](http://html.mh-extra.com/html/knick/stratos-pro-a401b-ph/stratos-pro-a401b-ph_user-manual_1980199106.webp)
106
Controller Functions
with:
Y
P
Proportional
action
T
N
Reset
time
[s]
T
D
Rate
time
[s]
K
C
Controller
gain
[%]
Constant 5 (for pH)
500
mV
(for
ORP)
Controller equations
Neutral zone
Tolerated deviation from desired value.
With the setting “1 pH”, for example, a deviation of ± 0.5 pH from the
desired value is tolerated.
+100 %
50 %
X
w
Process variables: pH/ (mV),
underneath: temp [K]
Con
tr
oller
output Y
K
C
= 500 %
K
C
= 200 %
K
C
= 100 %
K
C
= 50 %
1 / (100)
2 / (200)
3 / (300)
4 / (400)
Proportional action (Gradient K
C
[%])
Deviation
5 / (500)
[10]
[20]
[30]
[40]
[50]
Controller output Y =
I action
D action
dY
P
dt
1
T
R
P action
Y
P
+
Y
P
dt
+ T
D
Proportional action Y
P
Setpoint - Meas. value
Constant
Y
P
=
* K
C
Summary of Contents for Stratos Pro A401B PH
Page 1: ...www knick de Latest Product Information Stratos Pro A401B PH User Manual 094698 ...
Page 11: ...11 Typical Application of Stratos Pro A401B PH IrDA ...
Page 42: ...42 ...
Page 50: ...50 Configuration Select Default Sensor SENSOR ISM for ISM sen sors only Configuration ...
Page 53: ...53 Configuration Configuration Choices Default Relay 1 2 RL1 RL2 Selected in text line ...
Page 104: ...104 ...
Page 148: ...148 ...