KMC Controls THE-1102 Installation Manual Download Page 2

THE-1102 

Installation Guide

© 2013 KMC Controls, Inc.   

861-019-01F

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Important Notices

The material in this document is for information 

purposes only. The contents and the product it de-

scribes are subject to change without notice. KMC 

Controls, Inc. makes no representations or warran-

ties with respect to this document. In no event shall 

KMC Controls, Inc. be liable for any damages, direct 

or incidental, arising out of or related to the use of 

this document.

Wiring

Maintenance

Careful installation will also ensure long-term 

reliability and performance. Remove dust as neces-

sary from holes in top and bottom. Clean with a soft, 

damp cloth and mild soap.

More Information

For controller configuration of the 

humidity input, see the relevant 

documentation for the controller 

and software. For controller con-

figuration of the thermistor input 

as well as mounting considerations, 

troubleshooting, and other informa-

tion, see also the relevant sections 

in the 

STE-6010/6011/6013/6015 

Application Guide

.

For THE-1102 specifications and 

accessory information, see the 

THE-1102 Data Sheet

.

For more information about using 

the THE-1102 with the REE-2002, 

see the 

REE-2002 Installation 

Guide

.

NOTE:  The early version of the THE-1102 had 

terminals marked A through F.

For power, connect the + side of a regulated 10–15 

VDC power supply to Terminal “D” and the – side to 

“F” (see the terminal diagram).

NOTE:  Signal ground and power ground are 

connected together internally.

Connect the temperature output (10K thermistor 

across Terminals “A” and “C”) to the controller’s 

temperature input. (Set the controller’s pull-up resis-

tor accordingly.)

Connect the humidity output (0 to 5 VDC across 

Terminals “B” and “C”) to the controller’s humidity 

input. (Set the controller’s pull-up resistor accord-

ingly.)

NOTE:  The internal thermistor and the 0 to 5 VDC 

humidity output have a common signal 

ground.

Alternately, use an REE-2002 (shown here but pur-

chased separately). See the 

REE-2002 Installation 

Guide

 for additional information about power and 

humidity output options.

REE-2002

24 VAC

GND

24 VAC

0-5 VDC

0-10

VDC

4-20

mA

F

C

D

B

THE-1102

Humidity Output

(0-5 VDC)

(Without the REE-2002, only the THE-1102’s 0-5 VDC humidity

output and thermistor signal are available to a controller)

Temp. Output

(10K Thermistor)

Signal Ground

– Power Ground

+ 10-15 VDC Power

F

C

D

B

A

Controller

Temp. Input

Signal Ground

Humidity Input*

+

Phase 

Neutral

*Load between Humidity Input and Signal Ground
  is 250 ohms min. to 650 ohms max. for 4-20 mA
  or 1000 ohms min. for VDC