background image

STE-6010/6011/6013/6015 Room Temperature Sensors 

Installation Guide

2.438

2.250

R 3.094

R .187

.643

.450

STE-6013

STE-6011

.475

max.

STE-6010/6015

Modular 

RJ-45 

Jack

Four-pin 

EIA-485 
PC Data 

Port

Clamp

(Screw-type) 

Terminals

Clamp

(Screw-type) 

Terminals

.149

Installation Guide

Room Temperature Sensors 

STE-6010/6011/6013/6015

 

Mounting 

1

Location and Cover Removal  1
STE-6010/6013/6015 Only 

1

STE-6011 Only 

1

Controller Connection  2

STE-6010/6015 

2

STE-6011 

2

STE-6013 

2

Maintenance 

2

More Information  2

Mounting

4.  Attach the cable to the terminal block or jack 

according to the appropriate wiring diagram on 

the next page.

5.  Replace the cover.

STE-6011 Only

Handy Box Installation (Recommended)

1.  Mount a universal backplate HMO-6036 to the 

handy box using the two screws provided.

2.  Remove the cover from the back panel.
3.  Attach wires according to the STE-6011 wiring 

diagram on the next page.

4.  Attach the back panel to the backplate using two 

screws.

5.  Check that leads to the thermistor are straight 

and the thermistor is completely extended.

6.  Replace the cover.

Hollow Wall Installation

1.  Remove the cover from the back panel.
2.  Use the back panel as a template to drill two 

holes for mounting screws (7/64 inches or 3 mm 

in diameter and 1.4 inches, 1-13/32 inches, or 35.6 

mm apart) and to cut a center hole (7/8 inch or 20 

mm) for the terminal block or jack.

3.  Attach wires according to the STE-6011 wiring 

diagram on the next page.

4.  Attach the back panel to the wall using two 

#6 self-threading screws. (Plastic anchors are 

recommended, and the size of the holes will then 

need adjusting.)

5.  Check that leads to the thermistor are straight 

and the thermistor is completely extended.

6.  Replace the cover.

All dimensions 

are in inches

Location and Cover Removal

Install the sensor on an inside wall where it can sense 

the average room temperature and be away from 

direct sunlight, heat sources, windows, air vents, 

and air circulation obstructions (curtains, furniture, 

etc.). It can be mounted on a hollow wall or (with 

a universal backplate HMO-6036/6036W) to a 2 x 4 

inch handy box.
The cover is held to the black, back panel by three, 

small, round pegs that fit in the holes of the cover. 

The bottom peg is on a tab and snaps into the center 

bottom hole.
1.  With a small Phillips screwdriver or hex wrench, 

press in and hold the tab button that snaps into 

the center hole on the bottom cover.

2.  Carefully pull or pry the back panel from the 

front cover.

STE-6010/6013/6015 Only

Handy Box Installation (Recommended)

1.  Mount a universal backplate 

HMO-6036 or HMO-6036W to the 

handy box using the two screws 

provided.

2.  Remove the cover from the back panel.
3.  Attach the back panel to the backplate using the 

two screws provided.

4.  Attach the cable to the terminal block or jack 

according to the appropriate wiring diagram on 

the next page.

5.  Replace the cover.

Hollow Wall Installation

1.  Remove the cover from the back panel.
2.  Using the back panel as a template, drill two holes for 

mounting screws (7/64 inches or 3 mm in diameter 

and 1.4 inches, 1-13/32 inches, or 35.6 mm apart) and 

cut a center hole (size needed is dependent on model) 

for the terminal block or jack.

3.  Attach the back panel to the wall using two 

#6 self-threading screws. (Plastic anchors are 

recommended, and the size of the holes will then 

need adjusting.)