background image

Contents

Specifications ............................................................... 2
Network cable preparation ........................................... 6
Rough-in preparation  ................................................... 6
Installing the NetSensor ................................................ 7
PC data port  ................................................................. 8
Operation .................................................................... 9
Maintenance .............................................................. 10
Programming ............................................................. 11

Installation and 

Operation Guide

NetSensor

KMD-1261 and KMD-1281

Motion, temperature and humidity 

sensors

®

903-019-10

 

Summary of Contents for NetSensor KMD-1261

Page 1: ...le preparation 6 Rough in preparation 6 Installing the NetSensor 7 PC data port 8 Operation 9 Maintenance 10 Programming 11 Installation and Operation Guide NetSensor KMD 1261 and KMD 1281 Motion temperature and humidity sensors 903 019 10 ...

Page 2: ...maller than 24 AWG Power 5 volts DC supplied from the connected controller Mounting Surface mount directly to any flat surface or to a 2 x 4 inch or 4 x 4 inch handy box Mounting on a 4 x 4 inch box requires a mounting backplate Weight 2 8 ounces 80 grams Material Light almond or white plastic Accessories Mounting backplate Almond 4 x 4 inch HMO 1161 White 4 x 4 inch HMO 1161W Gasket HPO 1161 Repl...

Page 3: ...00 Relative humidity Accuracy at 25 C 2 from 10 90 Relative humidity Response time Less than or equal to 4 seconds Temperature Accuracy 0 9 F 0 5 C Offset from 40 to 104 F 4 4 to 40 0 C Offset is adjusted through configuration software Resolution 0 1 F 0 1 C Operating range 36 to 120 F 2 2 to 48 8 C Response time 5 to 30 seconds Environmental Limits Operating Temperature 34 to 125 F 1 1 to 51 6 C ...

Page 4: ...KMC Controls 4 Dimensions A B C D E F 3 25 in 5 16 in 2 58 in 3 25 in 0 87 in 1 07 in 83 mm 131 mm 66 mm 83 mm 22 mm 27 mm A C D E B F ...

Page 5: ...of 2 indicates no motion A value of 0 or 1 indicates the auxiliary function is active The value of the auxiliary function will remain at 0 for approximately 30 seconds after power is applied to the NetSensor Models Temperature only Almond KMD 1261 White KMD 1261W Temperature and humidity Almond KMD 1281 White KMD 1281W 55 10 m 32 8 ft 10 m 32 8 ft X 0 10 m 32 8 ft 10 m 32 8 ft 0 46 5 Y Top view Si...

Page 6: ... 75 feet 22 9 meters Cable conductors must be no smaller than 24 AWG Cable insulation must meet local building codes Connectors must be appropriate for the cable in use and are installed following the connector manufacturers instructions Rough in preparation Caution To prevent mounting screw heads from touching the circuit board in the NetSensor use only the mounting screws supplied by KMC Control...

Page 7: ...rom the mounting base to remove it 2 Route the RJ 12 cable through the mounting base 3 Fasten the mounting base directly to a 2 x 4 inch outlet box or a backplate with the Allen screws toward the floor 4 Insert the RJ 12 cable coming from the base into the NetSensor 5 Place the top of the NetSensor over the top of the mounting base and swing it down over the Allen screw brackets Be careful not to ...

Page 8: ...5576 USB Communicator see the illustration above For a serial port connection to BACstage use a third party interface For serial port connection to WinControl use a KMD 5559 CommTalk and KMD 5624 cable To use the PC data port 1 Connect the keyed flat end of the KMD 5624 NetSensor interface cable to the port on the NetSensor The KMD 5624 cable is included with the KMD 5576 but not the KMD 5559 2 Co...

Page 9: ...tion of the programmable buttons depend upon the program in the controller to which the NetSensor is connected See Programming on page 11 The arrow buttons adjust the programmed values up or down Values can be changed for all programmed buttons except the setpoint as follows 1 Press the button for the desired function 2 Adjust the value up or down Setpoint Pressing either the up or down arrow butt...

Page 10: ...KMC Controls 10 Maintenance Remove dust as necessary from holes in top and bottom Clean the display and motion sensor cover with a soft damp cloth and mild soap ...

Page 11: ...on numbers Table 1 lists the settings for programming a NetSensor with WinControl Use the NetSensor dialog found under the Control Menu to configure each button Table 2 lists settings for programming a NetSensor with BACstage Use the NetSensor dialog in the Device Menu to configure each button Additional instructions on programming a NetSensor are included in the program help for WinControlXL BACs...

Page 12: ...ange Display Units Type 1 Temperature Analog F or C Read Only Deg F Deg C Analog 2 Setpoint Analog 0 Decimal Read Write Deg F Deg C Analog 5 Time Analog Time Read Write Time Analog 7 Humidity KMD 1281 only Analog 0 Decimal Read Write RH Analog Aux Auxiliary and Motion Analog 0 Decimal Read Write Unused Analog ...

Page 13: ...nge the value The setting in Range WinControl or Display Format BACstage sets the NetSensror display to either Fahrenheit or Celsius Table 2 Settings for BACnet controllers NetSensor configuration Variable Button Function Assignment Display format Permission Object type Units 1 Temperature AV F or C Read Only AV F or C 2 Setpoint AV 0 Read Write AV F or C 5 Time AV Time Read Only AV Hours 7 Humidi...

Page 14: ...rs or an analog value object in BACnet controllers Add a Control Basic line as follows 10 VAR5 TIME Verifying a functioning NetSensor Use NETSENSOR STATUS in a Control Basic program to check if a functioning NetSensor is connected to the controller 10 IF NOT NETSENSOR STATUS THEN STOP OUT1 Verifying firmware version Simultaneously push Button 1 and Button 4 to display the version of the firmware i...

Page 15: ...NetSensor Installation and Operation 15 ...

Page 16: ...any means without the written permission of KMC Controls Inc Printed in U S A Disclaimer The material in this manual is for information purposes only The contents and the product it describes are subject to change without notice KMC Controls Inc makes no representations or warranties with respect to this manual In no event shall KMC Controls Inc be liable for any damages direct or incidental arisi...