CTE-5001/5011
1
Installation Guide
Installation Guide
Room Thermostats, Single Setpoint, DA Cooling or RA Heating
CTE-5001/5011
Mounting
Mounting
1
Connections and Wiring 1
Adjustments and Calibration 3
Maintenance
3
Accessories
3
Important Notices 3
NOTE: See the data sheet for specifications.
•
Attach the optional adapter backplate (see the
Accessories section) to a standard 2" x 4" (51 x 102
mm) handy box or directly to a hollow wall.
• Remove the cover and, u
sing the two 6-20
self-threading screws (included), attach the
thermostat to the backplate.
Connections and Wiring
See the basic instructions below and the diagrams
on the next page. The first sample application on
the next page illustrates basic DA cooling. The sec-
ond sample application illustrates DA cooling with
RA heating changeover.
• Terminal A:
For
Direct Action
, jumper to
terminal
B
; or for
Reverse Action
, connect to
terminal
5
of the CEP/CSP-4xxx controller/
actuator.
• Terminal B
: Connect to CEP/CSP-4xxx terminal
4
.
• Terminal C:
For
DA
, connect to CEP/CSP-4xxx
terminal
5
; or for
RA
, jumper to thermostat
terminal
B
.
• Terminal D:
Connect to the CEP/CSP-4xxx
In
terminal
6
.
• Terminal E:
To override to full
close
, connect
to CEP/CSP-4xxx terminal
5
; or to override full
open
, connect to CEP/CSP-4xxx terminal
4
.
• Terminal F
: For optional flow readout at
thermostat test points, connect to the CEP/CSP-
4xxx
Out
terminal
7
.