CTE-5001/5011 

Installation Guide

Installation Guide

Room Thermostats, Single Setpoint, DA Cooling or RA Heating

CTE-5001/5011

Mounting

Mounting 

1

Connections and Wiring  1
Adjustments and Calibration  3
Maintenance 

3

Accessories 

3

Important Notices  3

NOTE:  See the data sheet for specifications.

• 

Attach the optional adapter backplate (see the 

Accessories section) to a standard 2" x 4" (51 x 102 

mm) handy box or directly to a hollow wall.

•  Remove the cover and, u

sing the two 6-20 

self-threading screws (included), attach the 

thermostat to the backplate.

Connections and Wiring

See the basic instructions below and the diagrams 

on the next page. The first sample application on 

the next page illustrates basic DA cooling. The sec-

ond sample application illustrates DA cooling with 

RA heating changeover.
•  Terminal A:

 For 

Direct Action

, jumper to 

terminal 

B

; or for 

Reverse Action

, connect to 

terminal 

5

 of the CEP/CSP-4xxx controller/

actuator.

•  Terminal B

: Connect to CEP/CSP-4xxx terminal 

4

.

•  Terminal C:

 For 

DA

, connect to CEP/CSP-4xxx 

terminal 

5

; or for 

RA

, jumper to thermostat 

terminal 

B

.

•  Terminal D:

 Connect to the CEP/CSP-4xxx 

In

 

terminal 

6

.

•  Terminal E: 

To override to full 

close

, connect 

to CEP/CSP-4xxx terminal 

5

; or to override full 

open

, connect to CEP/CSP-4xxx terminal 

4

.

•  Terminal F

: For optional flow readout at 

thermostat test points, connect to the CEP/CSP-

4xxx 

Out

 terminal 

7

.