background image

CSP-4702 

    4 

Installation Guide

Static Pressure Control

Besides VAV applications, the CSP-4702 can also act 

as a static pressure controller in such applications as 

AHU or RTU bypass control. It is not then connected 

to a thermostat. For information, see the 

CSP-4702 

Static Pressure (Bypass) Control Application 

Guide

.

© 2018 KMC Controls, Inc.   

036-019-04F

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

More Information

For specifications, 

see the

 

CSP-4702 Data Sheet

 on 

the KMC web site.
For applications (with the CTE-5202 thermostat) 

and other information, see the 

CTE-5202 Applica-

tions Guide

.

For information about using the CSP-4702 as static 

pressure controller in AHU/RTU bypass applica

-

tions, see the 

CSP-4702 Static Pressure (Bypass) 

Control Application Guide

.

Troubleshooting

No Rotation

NOTE:

  For about 15 seconds after power is applied, 

no rotation occurs and one or both of the 

LEDs will flash.

• 

Check that the shaft moves freely. (Press and 

hold the gear disengagement lever and manually 

rotate the shaft.)

• 

Check wiring. (See Wiring Issues section below.)

• 

Check for a tripped circuit breaker to the 

transformer, for proper supply voltage from the 

transformer (or power supply), and for enough 

capacity (VA) for all connected devices. See their 

respective data sheets and 

Tips for Connecting 

24-Volt Power Application Note (AN0604D)

 

available on the KMC Controls web site.

• 

Check that the direction jumper is in the proper 

position. See 

Rotation Direction on page 2

.

• 

Check the polarity and level of the input signal 

from the thermostat.

Wrong Rotation Direction or Stroke Range

• 

Check the position of the direction jumper. See 

Rotation Direction on page 2

.

• 

Check the flow limits (on the controller and the 

thermostat). See 

Min. and Max. Flow Limits on 

page 3

.

• 

Check the adjustable stop position.

No Pressure Output Signal

• 

Check the wiring. (See Wiring Issues section 

below.)

• 

Check air flow and sensor. Tubing should be free 

of kinks and restrictions. Sensor must be oriented 

in the correct airflow direction.

Wiring Issues

• 

Check for correct wiring at the each device.

• 

Use a voltmeter and ohmmeter to check the 

terminals for expected values.

• 

See 

Tips for Connecting 24-Volt Power Applica-

tion Note (AN0604D)

.

NOTE:  Wiring must be adequate to avoid 

excessive voltage drop on long runs! Allow 

plenty of “cushion” in measurements. A 

meter may be too slow to register transient 

dips or peaks during startup.

Important Notices

The material in this document is for information 

purposes only. 

The contents and the product it 

describes are subject to change without notice.

 

KMC Controls, Inc. makes no representations or 

warranties with respect to this document. In no event 

shall KMC Controls, Inc. be liable for any damages, 

direct or incidental, arising out of or related to the 

use of this document.
This device complies with Part 15 of the FCC Rules. 

Operation is subject to the following two conditions: 

(1) this device may not cause harmful interference, 

and (2) this device must accept any interference 

received, including interference that may cause 

undesired operation. This Class B electronic appara

-

tus complies with Canadian ICES-003.

Summary of Contents for CSP-4702

Page 1: ...Crank Arm Kit NOTE For VAV applications with the analog CTE 5202 thermostat see the CTE 5202 Applications Guide For static pressure controller applications see the CSP 4702 Static Pressure Bypass Control Application Guide The CSP 4702 mounts directly to 1 4 to 5 8 inch 6 to 16 mm round shafts or 1 4 to 7 16 inch 6 to 11 mm square shafts 1 Ensure the damper can move freely through its entire range ...

Page 2: ... see the CSP 4702 Static Pressure Bypass Control Application Guide NOTE For VAV applications the SSS 1000 series differential pressure flow sensor must be mounted with the arrow pointing in the direction of the air flow To connect to 1 4 inch tubing from the CSP 4702 an SSS 100x differential pressure flow sensor requires a 3 8 to 1 4 barb union adapter and 1 of 3 8 OD x 0 062 FR tubing for both co...

Page 3: ...ect either the controller s or the thermostat s limits Limits Set at the CSP 4702 To set the minimum and maximum flow limits at the CSP 4702 with thermostat supplying 2 10 VDC 1 Ensure the thermostat output is 2 10 VDC For the CTE 5202 thermostat see the CTE 5202 Applications Guide 2 Loosen the screw on the conduit fitting and lift up to remove the fitting 3 Connect a voltmeter to the meter taps T...

Page 4: ...sition See Rotation Direction on page 2 Check the polarity and level of the input signal from the thermostat Wrong Rotation Direction or Stroke Range Check the position of the direction jumper See Rotation Direction on page 2 Check the flow limits on the controller and the thermostat See Min and Max Flow Limits on page 3 Check the adjustable stop position No Pressure Output Signal Check the wiring...

Reviews: