Output objects
The following BACnet output objects represent values at the physical outputs
of the AppStat. For output wiring details see
.
For application specific wiring details see the section
.
Note:
Not all objects are present in every model.
Output
Name
Description
Device type
AO6
VALVE
Analog Valve Output
0-100% (0-10 V)
AO7
AUX HEAT
Auxiliary Heat
0-100% (0-10V)
AO8
FAN_SPEED_AO
Fan Speed Control
0-100% (0-10V)
BO1
LOW
Fan Low Speed
Unknown
BO1
FAN_START_STOP
Fan Start/Stop
Unknown
BO2
MEDIUM
Fan Medium Speed
Unknown
BO3
HIGH
Fan High Speed
Unknown
BO4
VALVE
Valve
Unknown
BO5
AUX HEAT
Auxiliary Heat
Unknown
Table 7–2
Fan coil unit, two-pipe
Output Name
Description
Device type
AO6
COOLING_VLV
Analog Cooling Output
0-100% (0-10 V)
AO7
HEATING_VLV
Analog Heating Output
0-100% (0-10 V)
AO8
FAN_SPEED_AO
Fan Speed Control
0-100% (0-10V)
BO1
LOW
Fan Low Speed
Unknown
BO1
FAN_START_STOP
Fan Start/Stop
Unknown
BO2
MEDIUM
Fan Medium Speed
Unknown
BO3
HIGH
Fan High Speed
Unknown
BO4
COOLING_VLV
Cooling Valve
Unknown
BO5
HEATING_VLV
Heating Valve
Unknown
Table 7–3
Fan coil units, four-pipe
Installation, Operation, and Application Guide for AppStat
Section 7: System integration
Revision G
115
Summary of Contents for BAC-4000 series
Page 6: ...Contents KMC Controls Inc 6 Revision G ...
Page 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Page 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Page 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Page 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Page 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...