BACnet objects
The AppStat is a BACnet Application Specific Controller (ASC) that is
composed of standard BACnet objects. This section lists the objects that are
likely to be needed for monitoring with a standard BACnet operator
workstation to verify system operation.
Caution
Changing the configuration of any object may result in
unpredictable operation of the AppStat and damage to
equipment that is under control of the AppStat.
Input objects
The following BACnet input objects represent values at the physical inputs of
the AppStat. Only inputs 1-3 are available for external connections. For input
wiring details see
. For application specific
wiring details see the section
.
Note:
Not all input objects are present in every model.
Input
Name
Description
Device type
Models
AI1
REMOTE_SENSOR
Remote Room Sensor
KMC10K_Type_II
All
AI2
WATER_TEMP
Water Temperature
KMC10K_Type_III
FCU only
AI2
OAT
Outdoor Air Temp
KMC10K_Type_III
HPU, RTU
AI3
DAT
Discharge Air Temperature
KMC10K_Type_III
All
AI4
LOCAL_SENSOR
Space Temperature
KMC10K_Type_II
All
AI5
HUMIDITY
Space Humidity
NONE
All
BI6
MOTION_SENSOR
Motion Sensor
Unknown
All
Table 7–1
AppStat Input objects
Section 7: System integration
KMC Controls, Inc.
114
Revision G
Summary of Contents for BAC-4000 series
Page 6: ...Contents KMC Controls Inc 6 Revision G ...
Page 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Page 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Page 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Page 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Page 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...