SMY133-SMY134-SMP133 Operating Manual
1. General
Measurement & Evaluation
•
three measurement voltage inputs, star / delta / Aron connection
•
three/four measurement current inputs for CTs nominal secondary output of 5/1 A or 0.1 A
•
10/12 periods evaluation cycle (200 ms at 50/60 Hz)
•
continuous ( gap-less) measurement of voltage and current
•
evaluation of harmonic components up to 50
th
•
fixed window / floating window average values of all evaluated quantities with minimum &
maximum values registration
•
built-in electricity meter :
◦
four-quadrant counters for both active and reactive energies at three tariffs
◦
single phase and three phase energies
◦
maximum of average active power value registration (maximum demand)
•
built-in thermometer
•
residual current inputs (certain models only)
Communication
•
USB 2.0 communication port for fast data acquisition, configuration and firmware upgrades
•
optional remote communication interface ( RS 485 / Ethernet / M-Bus)
•
proprietary protocol with free data acquisition software ENVIS
•
MODBUS RTU /TCP protocols for simple integration with third party SCADA software
•
embedded webserver ( for instruments with Ethernet interface )
Datalogging Capabilities
•
battery backed real time circuit (RTC)
•
record interval from 0.2 second up to 1 hour
•
high memory capacity for programmable recording of aggregated measurement values
•
automated electricity meter readings at preselected time intervals
Inputs & Outputs ( Depending on Instrument Model )
•
digital outputs (relays or solid state)
•
digital inputs
•
0 ÷ 20 mA
DC
analog inputs
•
Pt100 temperature sensor input
Design
•
96x96 mm plastic box for panel mounting
•
TFT-LCD colour graphic display, 5 keys