Klinger Minimag
Operation Manual
KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | [email protected] | www.klinger.dk
Side 13
Fig.6.2 Example for the effect of rate-of-change limit
6.1.3.2.9 Total Unit
The converter has three 10-digit counters and the maximum counts are 9999999999. The
total flow unit can be L, m
3
, US gallon, Imperial gallon, kg or t (metric ton) with a multiplying factor
of 0.001, 0.01, 0.1, 1, 10, 100 or 1000.
6.1.3.2.10
Flow Density
The converter is capable of measuring mass flow if fluid density is set. The density can be set
from 0.0001 to 3.9999 and the mass unit is determined automatically by flow unit. The density
should be set to 1.0000 (default value) if not used. Otherwise, measurement data will be forced to
nil.
6.1.3.2.11
Current Type
Current output type is selectable from 4-20mA to 0-10mA.
6.1.3.2.12
Pulse Output
Two types of pulse output are available to choose from: frequency output mode and pulse
output mode. The meter outputs continuous square wave pulse under frequency mode, while
pulse series under pulse mode. Frequency output is usually used for flow rate measurement