![Klimawent ERGO-KOS-AL Use And Maintenance Manual Download Page 10](http://html1.mh-extra.com/html/klimawent/ergo-kos-al/ergo-kos-al_use-and-maintenance-manual_1977936010.webp)
10
extraction rail
ERGO-KOS-AL
30.01.2019
Table No.3
Type of the fan
Synchronous
rotations
[r.p.m.]
Supply
voltage
[V]
Motor
rate
[kW]
Ingress
protection
IP
Acoustic
pressure level
[dB(A)]
from distance
Maximum
volume flow
[m
3
/h]
Maximum
vacuum
[Pa]
Weight
[kg]
1m
5m
WPA-5-D-1-N
3000
230
0,37
54
73/67* 59/53*
1900
1250
23
WPA-5-D-3-N
3 x 400
WPA-6-D-1-N
3000
230
0,75
54
78/75* 64/61*
2500
1700
28
WPA-6-D-3-N
3 x 400
WPA-7-D-1-N
3000
230
1,1
54
81/74* 67/60*
3100
1800
30
WPA-7-D-3-N
3 x 400
WPA-8-D-3-N
3000
3 x 400
1,5
54
82/78* 68/64*
3900
2050
36
WPA-9-D-3-N
3000
3 x 400
2,2
54
86/82* 72/68*
4500
2400
45
WPA-10-D-3-N
3000
3 x 400
3,0
54
87/81* 73/67*
6200
2450
58
WPA-11-D-3-N
3000
3 x 400
5,5
54
91/88* 77/74*
8050
2950
77
WPA-13-D-3-N
3000
3 x 400
7,5
54
95/90* 81/76*
10800
3300
98
Prior to operational use switch on the extraction fan and make sure that the installation is
functioning properly.
7.
Operational Use
Low displacement resistance of the suction trolley and easy manoeuvring with the extraction
arm provide a convenient use of the whole extraction system. By means of the shut-off dam-
per lever, adjust the volume flow of the extracted air, in a way that efficiently eliminates the
fume and dustiness, not causing excessive draft.
During the operational use, the position of the extraction arm and of the shut-off lever can be
changed several times adapting the system to the current needs of User.
Having completed the work close the shut-off damper (in the suction hood), as this will impro-
ve the suction capacity in the second extraction arm.
One suction duct provides operational space for simultaneous function of two extraction arms.
Adjustment of the brakes (in the arm joints), ought to be performed according to the individual
instructions of the subsequent extraction arms.
8.
Troubleshooting Guide
Table No.4
Problem
Possible reason
Remedial measure
1.
The extraction arm is falling. Improperly adjusted frictional
Increase the tension upon frictio-
falling
brake in the joint
nal disks of the brake in the joint
by tightening the adjustment nuts
2.
Drop in the air suction rate
Improper impeller rotation sense Change the phase connection
along with the increased
of the extraction fan
sequence
noise level of the extraction The mesh holes of the inlet net Clean them using a wire brush
installation and arm
are clogged
Suddenly occurring vibra-
Foreign matter / object got stuck Disconnect the motor and
tions of the fan
within the impeller
remove the object
Impeller failure