37
4
Quadrant
Energy Analyzer
4
Quadrant
Energy Analyzer
NOTE:
Assigned values also applies to the 4 quadrant counters.
("Exp. active "," Reactive R1 "," Reactive R2, " , " Reactive R3"," Reactive R4 ")
3.2.1.1.3.3 T1_3 StartTime
‘T1_3’ abbreviation refers to the third time slice of tariff 1 me er.
T1_3 start time can be adjusted between 0-23 (for Virtual Keyboard
“T1 rate3” meter (the second time slice of T1 meter - T1_3) counts between T1_3 start
time and T1_1 start time.
E.g.:
Assume that ‘T1_3 start time’ and ‘T1_1 start time’ are adjusted as 0 and 8 respectively.
“T1 rate 3 meter (T1_3)” counts starting from 16:00 and ceases at 00:00.
Settings->Setup->Energy
T1_1 start time
8
hr
T1_2 start time
16
hr
T1_3 start time
0
hr
Start of day
0
hr
Start of month
1
T1 kWh
1000.0
kWh
T1 kWh E.
1000.0
kWh
T1 kVArh Imp. I.
1000.0
kVArh
T1 kVArh Imp. C. 1000.0
kVArh
T1 kVArh Exp. I.
1000.0
kVArh
T1 kVArh Exp. C. 1000.0
kVArh
T2 kWh
1000.0
kWh
Meters->Imp. active
T1 rate 2
1000.0
kWh
T1
1000.0
kWh
T2
1000.0
kWh
T1 rate 1
1000.0
kWh
T1 rate 3
1000.0
kWh
Fig. 3-27
T1_3 start time
NOTE:
Assigned values also applies to the 4 quadrant counters.
("Exp. active "," Reactive R1 "," Reactive R2, " , " Reactive R3"," Reactive R4 ")
SECTION 3 MENUS
If T1_1 and T1_2 have the same value, T1_1 and T1_3 counters count; If T1_1 and
T1_3 have the same value T1_1 and T1_2 counters count; if T1_2 and T1_3 have the
same value; T1_1 and T1_2 counters count, If T1_1, T1_2 and T1_3 have the same
value, only T1_1 counter will count.
Summary of Contents for Klea 320P-D
Page 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Page 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Page 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Page 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Page 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Page 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Page 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...