3

Cabinet dimensions

Product dimensions

92-1/2" 
(235 cm)
min.
111-1/2" 
(283.2 cm)
max.
ceiling to
floor

Venting requirements

The size of the vent should be uniform.

Use no more than three 90° elbows.

Make sure there is a minimum of 24" (61 cm) of straight
vent between the elbows if more than one elbow is used.

Do Not install two elbows together.

The length of vent system and number of elbows should
be kept to a minimum to provide efficient performance.

The vent system must have a damper. If roof or wall cap
has a damper, Do Not use damper supplied with the
range hood.

Use duct tape to seal all joints in the vent system.

Use caulking to seal exterior wall or roof opening around
the cap.

Determine which venting method is best for your
application and follow “Preparation” under ”Installation
steps“ on Page 5.

For the most efficient and
quiet operation:

Vent system must terminate to the outside.

Do not terminate the vent system in an attic or other
enclosed area.

Do not use 4 inch (10.2 cm) laundry-type wall caps.

Use metal vent only. Rigid metal vent is recommended. Do
not use plastic or metal foil vent.

30" hood  29-15/16" (76 cm),
36" hood  35-3/8" (89.9 cm),
48" hood  47-1/4" (120 cm)
overall width

23" (58.4 cm) min. -
42" (106.7) max.
overall chimney
height

22" (58.9 cm)
lower
chimney
height

1" (2.5 cm) min. - 
20" (50.8 cm) max.
upper chimney height

9-1/2" (24.1 cm)
canopy height

19-1/4" 

(48.9 cm)

overall depth

5-7/8" 

(14.9 cm)

10-7/8" 

(27.6 cm)

19" (48.3 cm)*

13" (33 cm)

cabinet

depth

34-5/8" 
(87.9 cm)
min.

18" (45.7 cm)
min. clearance
upper cabinet to
countertop

* If the canopy hood is installed higher than 

24" (61 cm) above the cooking surface, the 
middle bracket must be installed at the 
bottom point of the upper chimney sleeve.

** If the canopy hood is mounted higher than 

24" (61 cm) above cooking surface, depending
on ceiling height, upper chimney may need to
be cut.

36" (91.4 cm)
base cabinet
height

30" hood  30" (76 cm),
36" hood  35-7/16" (90 cm)
48" hood  47-5/16" (120.2 cm)
min. cabinet opening widths 

24" (61 cm) min.
bottom of canopy to
cooking surface**

Summary of Contents for (76.)(91.)(121.)

Page 1: ...Homeowner Keep Installation Instructions for future reference Save Installation Instructions for local electrical inspector s use 4329224 9763386 Quick Reference Table of Contents Pages Before you start Product dimensions Cabinet dimensions Venting requirements Electrical requirements Installation steps Use and Care Information Wiring diagram Accessories Warranty Requesting Assistance or Service 2...

Page 2: ...ty knife WARNING TO REDUCETHE RISK OF FIRE ELECTRIC SHOCK OR INJURYTO PERSONS OBSERVETHE FOLLOWING Installation work and electrical wiring must be done by qualified person s in accordance with all applicable Codes and Standards including Fire Rated Construction The combustion airflow needed for safe operation of fuel burning equipment may be affected by this unit s operation Follow the heating equ...

Page 3: ... not terminate the vent system in an attic or other enclosed area Do not use 4 inch 10 2 cm laundry type wall caps Use metal vent only Rigid metal vent is recommended Do not use plastic or metal foil vent 30 hood 29 15 16 76 cm 36 hood 35 3 8 89 9 cm 48 hood 47 1 4 120 cm overall width 23 58 4 cm min 42 106 7 max overall chimney height 22 58 9 cm lower chimney height 1 2 5 cm min 20 50 8 cm max up...

Page 4: ... m 0 8 cm 90 elbow 5 0 feet 5 0 feet 1 5 m 1 5 m 90 flat elbow 12 0 feet 3 7 m transition to round 5 0 feet 1 5 m wall cap 0 0 feet 0 0 m 3 1 4 x 10 8 3 cm x 25 cm elbow wall cap Maximum length 35 ft 10 7 m 1 90 elbow 5 ft 1 5 m 8 ft 2 4 m straight 8 ft 2 4 m 1 wall cap 0 ft 0 m Length of 3 1 4 x 10 8 3 cm x 25 cm system 13 ft 4 m 6 ft 1 8 m 2 ft 0 6 m 3 1 4 x 10 8 3 cm x 25 cm vent system To calc...

Page 5: ... clearance within the ceiling or wall for exhaust vent 1 If possible disconnect and move freestanding or slide in range from cabinet opening to provide easier access to rear wall Otherwise put a thick protective covering over countertop cooktop or range to protect from damage or dirt Select a flat surface for assembling the unit Cover that surface with a protective covering and place all canopy ho...

Page 6: ...e hood and adjust hood height by turning the adjusting screws Electrical connection Electrical Shock Hazard Disconnect power before making electrical connections Connect ground wire to green ground screw in terminal box Failure to do so can result in death or electrical shock WARNING 11 Make electrical connection Connect the power supply cable to hood terminal box through the U L or C S A listed c...

Page 7: ...rn blower and light off If range hood does not operate Check that the circuit breaker is not tripped or the house fuse blown Disconnect power supply Check that wiring is correct 18 The canopy hood controls are located in a grey panel on underside of the canopy To open the panel press on the front edge of panel and release The control panel will drop down 16 Place filters in canopy open ings so rea...

Page 8: ...ER including wet dishcloths or towels a violent steam explosion will result Use an extinguisher ONLY if You know you have a Class ABC extinguisher and you already know how to operate it The fire is small and contained in the area where it is started The fire department is being called You can fight the fire with your back to an exit Operating the light ON Move the light switch to the 1 position OF...

Page 9: ...378618 back 35 3 8 90 cm long Charcoal Filters Part No 4378623 2 per pkg Non Vented Recirculating Kits Part No 4378621 stainless steel Part No 4378622 white Part No 8171290 biscuit Wire Rack Chrome only Part No 8171297 30 76 2 cm Part No 4378616 36 91 4 cm Part No 8171298 48 121 9 cm Rack Hanger Kit Chrome only Part No 4378617 Chimney Extensions Part No 8171313 stainless steel Part No 8171315 bisc...

Page 10: ...systems resulting from unauthorized modifications made to the appliance 8 Expenses for travel and transportation for product service in remote locations 9 The removal and reinstallation of your appliance if it is installed in an inaccessible location or is not installed in accordance with published installation instructions DISCLAIMER OF IMPLIED WARRANTIES LIMITATION OF REMEDIES CUSTOMER S SOLE AN...

Page 11: ...tchenAid Factory Service at 1 800 442 1111 For further assistance If you need further assistance you can write to KitchenAid with any questions or concerns at KitchenAid Brand Home Appliances Customer Interaction Center c o Correspondence Dept 2000 North M 63 Benton Harbor MI 49022 2692 Please include a daytime phone number in your correspondence Use and maintenance procedures Accessory and repair...

Page 12: ... 361 3032 South Shore Montreal 1 800 361 0950 Quebec City 1 800 463 1523 Sherbrooke 1 800 567 6966 ATLANTIC PROVINCES 1 800 565 1598 For further assistance If you need further assistance you can write to KitchenAid Canada with any questions or concerns at Consumer Relations Department KitchenAid Canada 1901 Minnesota Court Mississauga Ontario L5N 3A7 Please include a daytime phone number in your c...

Page 13: ...server les instructions d installation à l intention de l inspecteur local des installations électriques 4329224 9763386 Référence rapide Table des matières Pages Avant de commencer Dimensions du produit Dimensions des placards Circuit de décharge de l air Alimentation électrique Les étapes de l installation Renseignements d utilisation et entretien Schéma de câblage Accessoires Garantie Demande d...

Page 14: ...s codes et normes applicables y compris les codes du bâtiment et de protec tion contre les incendies Le fonction nement de cet appareil peut modifier la cir culation de l air et affecter le fonction nement d un appareil utilisant un com bustible Respecter les directives du fabri cant de l équipement de chauffage et les prescriptions des normes de sécurité comme celles publiées par la National Fire...

Page 15: ...étanchéité avec du ruban adhésif pour conduit Autour de la bouche de décharge à l extérieur assurer l étanchéité avec un produit de calfeutrage Déterminer la méthode d évacuation de l air la plus appropriée pour l application et exécuter la préparation décrite dans les étapes de l installation à la page 5 Cheminée hauteur totale 58 4 cm 23 po min à 106 7 cm 42 po max Cheminée section inférieure 58...

Page 16: ...5 m 5 pi rectangle rond bouche de décharge 0 m 0 pi murale coude 8 3 x 25 cm 3 1 4 x 10 po bouche de décharge murale Longueur maximale 10 7 m 35 pi 1 coude à 90 1 5 m 5 pi Section droite 2 4 m 8 pi 2 4 m 8 pi 1 bouche de décharge murale 0 m 0 pi Longueur effective de conduit de 8 3 x 25 cm 3 1 4 x 10 po 4 m 13 pi 1 8 m 6 pi 0 6 m 2 pi Système de décharge 8 3 x 25 cm 3 1 4 x 10 po Pour calculer la ...

Page 17: ...la bride inférieure sur le mur à la hauteur indiquée La dimension Préparation indiquée à la page 3 correspond au montage de la hotte à 61 cm 24 po au dessus de la table de cuisson Lors de l installation de la bride inférieure orienter vers le bas les pattes de retenue sur lesquelles la hotte reposera Si un dosseret doit être utilisé avec cette hotte on DOIT l installer avant la hotte Les instructi...

Page 18: ... conduit homologation UL ou ACNOR Raccorder ensemble avec un connecteur de fils le conducteur blanc du câble d alimentation et le conducteur blanc de la hotte raccorder ensemble avec un connecteur de fils le conducteur noir du câble d alimentation et le conducteur noir de la hotte Connecter sous la vis verte le conducteur vert ou vert et jaune du câble d alimentation utilisé pour la liaison à la t...

Page 19: ...ateur et l extinction de la lampe Si les composants de la hotte ne fonctionnent pas correctement Déterminer si le circuit d alimentation de la hotte est alimenté disjoncteur ouvert ou fusible grillé Déconnecter la hotte du circuit d alimentation Vérifier que le câblage a été correctement réalisé 18 Les organes de commande de la hotte sont placés derrière une plaque grise sur la surface inférieure ...

Page 20: ...t pas immédiatement ÉVACUER LA PIÈCE ET CONTACTER LES POMPIERS NE JAMAIS PRENDRE EN MAIN UN RÉCIPIENT ENFLAMMÉ le risque de brûlure est élevé NE PAS UTILISER D EAU ni un torchon humide ceci pourrait provoquer une explosion de vapeur brûlante Utiliser un extincteur SEULEMENT si Il s agit d un extincteur de classe ABC dont on connaît le fonctionnement Il s agit d un petit feu encore limité à l endro...

Page 21: ...oxydable Pièce n 4378622 blanc Pièce n 8171290 biscuit Râtelier Chrome seulement Pièce n 8171297 76 2 cm 30 po Pièce n 4378616 91 4 cm 36 po Pièce n 8171298 121 9 cm 48 po Suspensoir pour râtelier Chrome seulement Pièce n 4378617 Extensions de cheminée Pièce n 8171313 acier inoxydable Pièce n 8171315 biscuit Pièce n 8171314 blanc Il est nécessaire de lire ces instructions avant d entreprendre l in...

Page 22: ...odification non autorisée faite à l appareil 8 Les frais de voyage ou de transport pour le service d un produit dans les régions éloignées 9 La dépose et la réinstallation de votre appareil si celui ci est installé dans un endroit inaccessible ou n est pas installé conformément aux instructions d installation fournies CLAUSE D EXONÉRATION DE RESPONSABILITÉ AU TITRE DES GARANTIES IMPLICITES LIMITAT...

Page 23: ... vous joindre dans la journée Nos consultants fournissent de l assistance pour Caractéristiques et spécifications de notre gamme complète d appareils électroménagers Renseignements concernant l installation Procédés d utilisation et d entretien Vente d accessoires et de pièces de rechange Assistance spécialisée aux clients langue espag nole malentendants malvoyants etc Les références aux marchands...

Page 24: ... 00 HNE en composant 1 800 422 1230 2 Si vous avez besoin de service Communiquer avec la succursale ou établissement de service autorisé de KitchenAid Canada le plus proche pour l entretien de votre appareil Voir liste ci dessous S assurer que la compagnie de service que vous contactez est autorisée à faire l entretien de votre appareil durant la période de garantie Si vous avez besoin de plus d a...

Reviews: