background image

8

CHIMNEY CONNECTION

Take into account the chimney’s location to insure 

it is not too close to neighbours or in a valley which 

may  cause  unhealthy  or  nuisance  conditions.  Your 

chimney  connector  and  chimney  must  have  the 

same diameter as the stove outlet (6”). If this is not 

the case, we recommend you contact your dealer 

in order to insure there will be no problem with the 

draft .

The  stove  pipe  must  be  made  of  aluminized  or 

cold roll steel with a minimum thickness of 0.021” or 

0.53mm. It is strictly forbidden to use galvanized steel.

Two basic types of chimneys are approved for use 

with solid fuel.  Factory-built and masonry.  Factory-

built chimney must comply with UL standard in the US 

and ULC standards for Canada.

Do  not  expect  your  stove  or  furnace  to  create 

draft.  Draft is not a function of the appliance.  Draft 

is purely a function of the chimney.  Modern stoves 

and furnaces are much more air-tight and efficient 

than  those  of  the  past,  and,  therefore,  require 

greater draft.  A minimum of .05" measured in water 

column  (gauges  to  measure  chimney  draft  are 

readily available at stove shops and are economical 

to  purchase  or  rent)  is  required  for  proper  drafting 

to  prevent  back-puffing,  smoke  spillage,  and  to 

maximize performance.

Chimneys  perform  two  functions  -  one  of  which 

is  apparent:    The  chimney  provides  a  means  for 

exhausting  smoke  and  flue  gases  resulting  from 

combustion  of  the  fuel.    Secondarily,  though,  the 

chimney  provides  "Draft"  which  allows  oxygen  to 

be  continuously  introduced  into  the  appliance,  so 

that  proper  combustion  is  possible.    As  of  April  1, 

1987, all wood heaters and furnaces manufactured 

by  6"(152mm)  chimney  that  meets  the  "Type  HT" 

requirement  and  complies  with  UL  103(2100°F, 

1149°C)  or  ULC  S629(650°C)  (when  a  factory  built 

chimney is used).

A chimney connector shall not pass through an attic, 

roof space, closet, floor, ceiling, or similar concealed 

space.    Where  passage  through  a  wall  or  partition 

of combustible construction is desired, the installation 

must conform with NFPA 211.

IMPORTANCE OF PROPER DRAFT

Draft is the force which moves air from the appliance 

up through the chimney. The amount of draft in your 

chimney depends on the length of the chimney, local 

geography,  nearby  obstructions  and  other  factors. 

Too much draft may cause excessive temperatures 

in  the  appliance  and  may  damage.  Inadequate 

draft  may  cause  backpuffing  into  the  room  and 

‘plugging’  of  the  chimney.  Inadequate  draft  will 

cause  the  appliance  to  leak  smoke  into  the  room 

through  appliance  and  chimney  connector  joints. 

An  uncontrollable  burn  or  excessive  temperature 

indicates excessive draft.

WARNING:

 Do not connect this unit to a chimney 

flue serving another appliance.

Summary of Contents for 2016E

Page 1: ...Before Starting The Installation or Operating This Heater Improper Installation Could Void Your Warranty Please read this entire manual before you install and use your new room heater Failure to follo...

Page 2: ...STM E2780 10 single Burn Rate Appendix and an efficiency of 66 6 This wood heater has a manufacturer set minimum low burn rate that must not be altered It is against federal regulations to alter this...

Page 3: ...ercial garbage Lawn clippings or yard waste Materials containing rubber including tires Materials containing plastic Waste petroleum products paints or paint thinners or asphalt products Materials con...

Page 4: ...e this heater who is unfamiliar with the correct operation of the heater 12 For additional information on using your Room Heater safely obtain a copy of the National Fire Protection Association NFPA p...

Page 5: ...vision that clearances may only be reduced by means approved by regulatory authority CAUTION Keep furnishings and other combustible materials away from the heater Stove Clearances A Side Wall 18 457mm...

Page 6: ...ns Check Figures 2 3 4 You should have at least the clearances shown from the heater and the connector pipe to combustible surfaces If you have a solid brick or stone wall behind your heater you can p...

Page 7: ...Heat Shield 891861 1 8 10AB x 3 8 Hex Screw 83172 12 N S 12 x 3 4 Teks Screw C23799 4 ASSEMBLY INSTRUCTIONS Step 1 THE BLOWER ASSEMBLY MUST BE DISCONNECTED FROM THE SOURCE OF ELECTRICAL SUPPLY BEFORE...

Page 8: ...Chimneys perform two functions one of which is apparent The chimney provides a means for exhausting smoke and flue gases resulting from combustion of the fuel Secondarily though the chimney provides D...

Page 9: ...lti layered construction It is designed to provide enough insulation and or air cooling so that the base back and sides can be safely placed in direct contact with combustible floors and walls Althoug...

Page 10: ...flue outlet requires a 6 152mm diameter for optimum drafting but can function well with an 8 203mm but becomes borderline beyond an 8 203mm diameter Masonry chimneys built of concrete blocks with or...

Page 11: ...fireclay at least 5 8 inch thick or metal thimble being sure that the thimble is flush with the inner flue lining secure the thimble in place with refractory mortar The thimble should be surrounded on...

Page 12: ...himney connector and a minimum 24 gage ventilated wall thimble which has two air channels of 1 25 4 mm each construct a wall pass through There shall be a minimum 6 152 4 mm separation area containing...

Page 13: ...The pipe cannot extend into the chimney flue Fig 8 5 Seal each connector pipe joint with furnace cement Also seal the pipe at the chimney 6 Use 3 sheet metal screws at each joint to make the piping ri...

Page 14: ...ocess as a vapor in the case of wood stoves the moisture in the wood being burned leaves the stove as a vapor The higher heating value is when water leaves the combustion process completely condensed...

Page 15: ...Do not expect a heater to draw It is the chimney that creates the draft Smoke spillage into the house or excessive buildup of water or creosote in the chimney are warnings that the chimney is not func...

Page 16: ...connector and chimney should be inspected at least once every two months during the heating season to determine if a creosote buildup has occurred If creosote has accumulated it should be removed to...

Page 17: ...ust be replaced using original manufacturers parts purchased through your dealer or directly from the appliance manufacturer Use of third party components will void the warranty 1 2 3 4 6 5 7 Key Part...

Page 18: ...irebrick Half 4 1 2 X 4 1 2 2 4 86645 Tube 7 32 Secondary Air 1 5 88250 Board Ceramic Fiber 2 In order to maintain warranty components must be replaced using original manufacturers parts purchased thr...

Page 19: ...r assembly must be disconnected from the source of electrical supply before attempting any maintenance Brick Placement Top Inside View Of Firebox 1 Insert right left side firebrick as shown 2 Insert r...

Page 20: ...tube and remove to allow the tube to be removed and replaced Whenever ashes get 3 to 4 inches deep in your firebox or ash pan and when the fire has burned down and cooled remove excess ashes Leave an...

Page 21: ...IONS 1 United States Stove Company shall not be liable for incidental consequential special or contingent damages anyone might suffer as a result of their breach of this written warranty or any implie...

Page 22: ...to the heater When ordering repair parts always give the following information as shown in this list 1 The part number _____________________________________ 2 The part description ___________________...

Page 23: ...___ Reason for Purchase qAlternative Heat qMain Heat Source qDecoration qCost qOther _________________________ What was the determining factor for purchasing your new appliance _______ I have read the...

Page 24: ...CUT HERE CUT HERE Fold Here Fold Here United States Stove Company P O Box 151 South Pittsburg TN 37380 Fold Here PLACE STAMP HERE...

Reviews: