Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
DO14
13
00014
Bit
DO1
4
Value, Read/Write, 0=Open,1=Close.
DO15
14
00015
Bit
DO1
5
Value, Read/Write, 0=Open,1=Close.
DO16
15
00016
Bit
DO1
6
Value, Read/Write, 0=Open,1=Close.
Notice
This Table corresponds to all MxxT series models, some of the models do not exist in the
corresponding channel then its register address is empty. For example, if DIN1 and DIN2 are available
for M100T, the DIN3 to DIN16 registers are empty.
8.1.3 Read Input Register
(Function Code 4: Read Input Register.)
Read Input Register (Function Code 4: Read Input Register.)
Channel
Register
Address
(Decimal)
PLC or
configuration
use address
(Decimal)
Data Type
Description
AIN1
0(High)
30001
(
High
)
32 Bit Int
ABCD
AIN1 Value, Read Only,
Real value= Current value stored in
register/100
1(Low)
30002
(
Low
)
AIN2
0(High)
30003
(
High
)
32 Bit Int
ABCD
AIN2 Value, Read Only,
Real value= Current value stored in
register/100
1(Low)
30004
(
Low
)
AIN3
0(High)
30005
(
High
)
32 Bit Int
ABCD
AIN3 Value, Read Only,
Real value= Current value stored in
register/100
1(Low)
30006
(
Low
)
AIN4
0(High)
30007
(
High
)
32 Bit Int
ABCD
AIN4 Value, Read Only,
Real value= Current value stored in
register/100
1(Low)
30008
(
Low
)
AIN5
0(High)
30009
(
High
)
32 Bit Int
ABCD
AIN5 Value, Read Only,
Real value= Current value stored in
register/100
1(Low)
30010
(
Low
)
AIN6
0(High)
30011
(
High
)
32 Bit Int
ABCD
AIN6 Value, Read Only,
Real value= Current value stored in
register/100
1(Low)
30012
(
Low
)
AIN7
0(High)
30013
(
High
)
32 Bit Int
ABCD
AIN7 Value, Read Only,
Real value= Current value stored in
register/100
1(Low)
30014
(
Low
)
AIN8
0(High)
30015
(
High
)
32 Bit Int
ABCD
AIN8 Value, Read Only,
Real value= Current value stored in
register/100
1(Low)
30016
(
Low
)
RTD1 ADC
0
30001
16 Bit int
RTD1 ADC Value, Read Only.
RTD 2 ADC
1
30002
16 Bit int
RTD2 ADC Value, Read Only.
RTD 3 ADC
2
30003
16 Bit int
RTD3 ADC Value, Read Only.