Page 15 of 56
King Pigeon Hi-Tech. Co., Ltd.
Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
DO wiring (sink)
5.4 RTD/AI/AO
The top terminal pins are multiplexed functions, and the specific function definitions are determined
according to the model selection table.
Tips:
Resistance Thermal Detector (RTD) compatibles 2-wire or 3-wire, please reference above mentioned wiring instruction. If
the sensor near the module and the wire resistance is small can be ignored, can be used 2-wire wiring, if the distance is far
and the wire resistance affect the value, should be used 3-wire way connection.
RTD/AI/AO
PT1+ ~ PT8+
1st ~ 8th PT100/PT1000 input positive
PT1- ~ PT8-
1st ~ 8th PT100/PT1000 input negative
GND
PT100/PT1000 input ground
AI1 ~ AI8
The 1st ~ 8th analog input positive
COM
The 1st ~ 8th analog quantity common terminal
AO1&AO2
1st & 2nd analog output positive
COM