PLC Data acquisition protocol conversion gateway
-D225
offline, count as one time, and then immediately
Connect, continue in sequence, and then perform
the time to connect to the server again in
accordance with the "dropped 3 times, reconnect
time".
Heartbeat time
The interval between sending heartbeat packets,
ranging from 1-9999 (seconds).
60
Note: (1) Select the transparent transmission protocol, the server configuration mainly configures
the server IP/domain name and port number. Whether to fill in other options according to your
needs.
(2) Choosing the King Pigeon (KPIOT )2.0 protocol and the King Pigeon 3.0 protocol is to connect to
the company's cloud platform, server IP/domain name and port number, heartbeat packet and
heartbeat response packet. The configuration software has been filled in by default, so be careful
not to modify it. Only need to fill in the configuration item of [Registration Package], please contact
our sales representative for [Registration Code] to fill in the content of [Registration Package]
(3) Select Modbus TCP Server protocol, the server configuration does not need to be configured,
so the server configuration items have been forbidden to fill in. Modbus TCP Server protocol is
used with the port number of this device
(4) The Modbus RTU Over TCP protocol is the Modbus RTU protocol of the independent platform
or other platforms. Please configure it according to the relevant configuration of the platform.
[Server IP/domain name] and [Slogan] are required
5
D225 Application case
The address of various PLC registers corresponds to the mapping address of D225 and what
function code is used to collect PLC register data. For details, see
Data acquisition of Mitsubishi PLC
Take Mitsubishi FX3U as an example, choose the server protocol as: Modbus TCP Server, and collect
the output Y and register D of FX3U. Mitsubishi FX3U and D225 equipment are connected through
RS422 to RS232 line.