INSTALLATION & MAINTENANCE MANUAL

SAVE THESE INSTRUCTIONS

for 

KCC & KCF SERIES CABINET HEATERS

   Congratulations

 on the purchase of your new 

KING ELECTRICAL CABINET WALL 

HEATER

. Your new heater has been designed and built to withstand heavyduty commercial 

and institutional usage. KCF models feature a whisper-quiet squirrel cage blower, with 
permanently lubricated bearings. Both models feature long-life heating elements with alumi-
num plate fins for rapid heat transfer. A variety of factory installed options allow this heater 
to be tailored to your specific application.

9131 - 10th Avenue South  Seattle Washington 98108

WARNING

T

HIS

 

UNIT

 

IS

 

MANUFACTURED

 

TO

 

OPERATE

 

ON

 

A

 

SPECIFIC

 

CONTROL

 

VOLTAGE

 

IN

 

COMPLIANCE

 

WITH

 

YOUR

 

ORDER

. S

TANDARD

 

CONTROL

 

VOLTAGES

 

ARE

 208 / 240 / 277 

FOR

 208 / 240 / 277 

VOLT

 

HEATERS

.  

24 V

OLT

 

CONTROL

 

IS

 

STANDARD

 

ON

 480 V

OLT

 

HEATERS

. 208 / 240 

OR

 277 V

OLT

 

HEATERS

 

MAY

 

ALSO

 

BE

 

ORDERED

 

WITH

 

AN

 

OPTIONAL

 24 V

OLT

 

CONTROL

. I

T

 

IS

 

IMPORTANT

 

THAT

 

YOU

 

VERIFY

 

YOUR

 

POWER

 

SUPPLY

 

VOLTAGE

 

WITH

 

THE

 

HEATER

 

THAT

 

YOU

 

HAVE

 

CHOSEN

. I

MPROPER

 

INSTALLATION

 

OR

 

FAILURE

 

TO

 

FOLLOW

 

THE

 

PROCEDURES

 

AS

 

OUTLINED

 

IN

 

THIS

 

MANUAL

 

CAN

 

RESULT

 

IN

 

SERIOUS

 

ELECTRICAL

 

SHOCK

.  

D

ISCONNECT

 

ALL

 

POWER

 

FROM

 

THE

 

HEATER

 

AT

 

THE

 

MAIN

 

SERVICE

 

PANEL

 

AND

 

LOCK

 

BEFORE

 

ATTEMPTING

 

TO

 

INSTALL

 

OR

 

SERVICE

 

THIS

 

UNIT

. A

LL

 

ELECTRICAL

 

WIRING

 

MUST

 

CONFORM

 

TO

 

LOCAL

 

ELECTRICAL

 

CODES

. H

EATER

 

CIRCUIT

 

MUST

 

BE

 

PROTECTED

 

WITH

 

THE

 

PROPER

 

SIZE

 

FUSES

 

OR

 

CIRCUIT

 

BREAKERS

.

KCC-KCF.indd : 4/08

Summary of Contents for KCC SERIES

Page 1: ...ashington 98108 WARNING THIS UNIT IS MANUFACTURED TO OPERATE ON A SPECIFIC CONTROL VOLTAGE IN COMPLIANCE WITH YOUR ORDER STANDARD CONTROL VOLTAGES ARE 208 240 277 FOR 208 240 277 VOLT HEATERS 24 VOLT CONTROL IS STANDARD ON 480 VOLT HEATERS 208 240 OR 277 VOLT HEATERS MAY ALSO BE ORDERED WITH AN OPTIONAL 24 VOLT CONTROL IT IS IMPORTANT THAT YOU VERIFY YOUR POWER SUPPLY VOLTAGE WITH THE HEATER THAT ...

Page 2: ...ory installed options are correct for the application Remove and set aside the grill Select power supply wire type and size to comply with local and national electric codes using heater rating given in table Connect wire to heater as shown in wiring diagram attached to cover Remove one of the knockouts from back of unit Secure power supply cable with clamps or run in conduit if required by local c...

Page 3: ...3 4830 3000 10 2 208 240 277 480 14 4 12 5 10 3 6 5 8 3 7 2 N A 3 6 36 45 2 68 190 KCF4 2040 KCF4 2440 KCF4 2740 KCF4 4840 4000 13 6 208 240 277 480 19 2 16 7 14 4 8 3 11 1 9 6 N A 4 8 48 55 3 102 285 KCF4 2050 KCF4 2450 KCF4 2750 KCF4 4850 5000 17 208 240 277 480 24 20 8 18 10 4 13 9 12 N A 6 48 55 4 102 285 AMPS Add Suffix 1 for Single Phase or 3 for Three Phase All 480V models require neutral w...

Page 4: ...NITS ONLY CONTACTOR HIGH LIMIT ELEMENT E L E M E N T E L E M E N T TYPICAL 3 PHASE WIRING 208 240 VOLT LINE VOLTAGE CONTROL L1 OPTIONAL DISCONNECT SWITCH L2 L3 CONTACTOR HIGH LIMIT TYPICAL 480V 3 PHASE WIRING 24 VOLT CONTROL E L E M E N T E L E M E N T ELEMENT NEUTRAL FAN S 1 2 or 3 FANS 277 VOLT 1 PHASE KCF UNITS ONLY REMOTE WALL THERMOSTAT OR OPTIONAL IN BUILT THERMOSTAT CONTROL TRANSFORMER 24V ...