6.15 Group C0
C0.00 Preset frequency 1
Lower limit of
frequency~upper limit of
frequency
【
5.00Hz
】
C0.01 Preset frequency 2
Lower limit of
frequency~upper limit of
frequency
【
10.00Hz
】
C0.02 Preset frequency 3
Lower limit of
frequency~upper limit of
frequency
【
20.00Hz
】
C0.03 Preset frequency 4
Lower limit of
frequency~upper limit of
frequency
【
30.00Hz
】
C0.04 Preset frequency 5
Lower limit of
frequency~upper limit of
frequency
【
40.00Hz
】
C0.05 Preset frequency 6
Lower limit of
frequency~upper limit of
frequency
【
45.00Hz
】
C0.06 Preset frequency 7
Lower limit of
frequency~upper limit of
frequency
【
50.00Hz
】
C0.07 Preset frequency 8
Lower limit of
frequency~upper limit of
frequency
【
5.00Hz
】
C0.08 Preset frequency 9
Lower limit of
frequency~upper limit of
frequency
【
10.00Hz
】
C0.09 Preset frequency 10
Lower limit of
frequency~upper limit of
frequency
【
20.00Hz
】
C0.10 Preset frequency 11
Lower limit of
frequency~upper limit of
frequency
【
30.00Hz
】
C0.11 Preset frequency 12
Lower limit of
frequency~upper limit of
frequency
【
40.00Hz
】
C0.12 Preset frequency 13
Lower limit of
frequency~upper limit of
frequency
【
45.00Hz
】
C0.13 Preset frequency 14
Lower limit of
frequency~upper limit of
frequency
【
50.00Hz
】
C0.14 Preset frequency 15
Lower limit of
frequency~upper limit of
frequency
【
50.00Hz
】
These frequencies will be used in multi-step speed
operation, refer to the introductions of No.27,28,29 and
30 function of A6.00
~
A6.04.
6.16 Group C1
Process close-loop control
The process closed-loop control type of CV100 is analog
close-loop control. Fig.6-39 shows the typical wiring of
analog close-loop control.
Fig.6-39 Analog feedback control system with
internal process close-loop
Analog feedback control system:
An analog feedback control system uses a pressure
transmitter as the feedback sensor of the internal
close-loop.As shown in Fig. 6-37, pressure reference
(voltage signal) is input via terminal AI2, while the
feedback pressure value is input into terminal AI1 in the
form of 0(4)~20mA current signal. The reference signal
and feedback signal are detected by the analog
channel.The start and stop of the drive can be controlled
by terminal Xi.
The above system can also use a TG (speed measuring
generator) in close speed-loop control.
CV10
U
M
QF
+10V
+10V
AI1
Xi
COM
P
AC
input
Pressure
transmitter
Output
V
W
PE
-10V
AI2
R
S
T
GND