Kimo CPE 310-S User Manual Download Page 1

Configuration of CPE 310-S and CPE 311-S

transmitters by keypad

Summary of Contents for CPE 310-S

Page 1: ...Configuration of CPE 310 S and CPE 311 S transmitters by keypad ...

Page 2: ......

Page 3: ... F190 12 5 F 200 Configuration of the channels and measurement units 13 5 1 Activate a channel 13 5 2 Assign a measurement unit to a channel 13 6 F 300 Manage the analogue outputs 14 6 1 Set the analogue outputs 14 6 2 Set the ranges of the analogue outputs 14 6 3 Output diagnostic 15 6 3 1 Connection configuration 15 6 3 2 Perform the output diagnostic 16 7 F400 Manage the alarms 17 8 F 500 Set t...

Page 4: ......

Page 5: ... to the previous step 1 3 Protection tips of the sensor It s extremely unwise to remove the protection tip of our hygrometry probes as the sensitive element is very fragile even to light contacts However if you have to remove the protection tip take all possible precautions and avoid any contact with the sensitive element To remove the protection tip unscrew it or unclip it Introduction 5 Up key D...

Page 6: ... register Registers type Type Size Description Format U8 1 byte Unsigned integer 8 bits Byte 1 Example with a value of 24 0x18 0x18 Type Size Description Format U16 2 bytes Unsigned integer 16 bits Byte 2 Byte 1 Example with a value of 300 0x012C 0x01 0x2C Type Size Description Format U32 4 bytes Unsigned integer 32 bits Byte 2 Byte 1 Byte 4 Byte 3 Example with a value of 1 096 861 217 0x4160C621 ...

Page 7: ... Unused Channel 3 Channel 2 Channel 1 Alarm state 1 the channel is in alarm state 0 the channel is not in alarm state Byte 4 Byte 3 b31 b28 b27 b26 b25 b24 b23 b20 b19 b18 b17 b16 Unused Relay 4 Relay 3 Relay 2 Relay 1 Unused Unused Alarm 3 Alarm 2 Alarm 1 1 the relay is triggered 0 the relay is not triggered 1 the alarm is activated 0 the alarm is deactivated Values Modbus code 7010 channel 1 704...

Page 8: ... speed 2400 4800 9600 19200 38400 115200 Unused Channel x Unit See list of unit Channel x Transmitter none probe 1 probe 2 module Unused Output x Type 4 20 mA 0 20 mA 0 10 V 0 5 V 0 1 V Unused Output x Diagnostic Deactivate 0 50 100 Unused Alarm x Mode Deactivate Rising edge Falling edge Monitoring Transmitt er state Unused Alarm x Security Negative Positive Unused Relay x Selection OFF ON Alarm 1...

Page 9: ... to the 4th 0 Press Up key to display 1 then press OK The following screen is displayed F 100 is for the number of the configuration folder There are 5 folders F 100 folder of the transmitter configuration See page 10 F 200 folder of the channels and measurement units Seer page 13 F 300 folder of the analogue outputs See page 14 F 400 folder of the alarms See page 17 F 500 folder of the channels i...

Page 10: ... blinks Press Up or Down key 1 blinks then press OK LOCK is displayed for a few seconds then the transmitter backs to the displaying of measured values All the keys are inactive To activate them again Press OK for 10 seconds LOCK is displayed for a few seconds then the transmitter goes back to the displaying of measured values and keys are active again 4 4 Modify the safety code F141 It is possibl...

Page 11: ...nd Down keys to select the required speed communication between the following values 2400 bds 4800 bds 9600 bds 19 2 Kbds 38 4 Kbds 115 2 Kbds Press OK F151 blinks with the selected speed communication below 4 6 Activate the options To activate an option an activation code is necessary This code is provided by the manufacturer Available options for CPE310 are the high resolution in pressure F170 s...

Page 12: ...lder is displayed Press Up key F 190 blinks and RAZ is displayed below Press OK OK is displayed below F190 Press OK to confirm the factory settings or Esc to cancel All the performed configurations will be erased 12 F 100 Configure the transmitter ...

Page 13: ...to activate the channel 1 of the transmitter To activate channels 2 and 3 go to the following folders F210 for channel 2 F220 for channel 3 Perform the same procedure as for the channel 1 5 2 Assign a measurement unit to a channel The transmitter is powered on and a channel is activated F 200 folder is displayed Press Up key F 201 sub folder is displayed with the unit corresponding to the channel ...

Page 14: ... CPE 310 S pressure transmitter 0 to 100 Pa with a reading in mmH2O the minimum and maximum ranges must be configured on a measuring range from 0 to 10 mmH2O See conversion chart page 16 The transmitter is powered on Press OK Enter the activation code see page 9 Press OK Press Up key to go to F 301 folder corresponding to the minimum range of the channel 1 Press OK The 1st digit of the minimum ran...

Page 15: ... setting of the type of output For a 0 10 V output signal the transmitter will generate 0 5 or 10 V For a 0 5 V output signal the transmitter will generate 0 2 5 or 5 V For a 4 20 mA output signal the transmitter will generate 4 12 or 20 mA 6 3 1 Connection configuration Before carrying out the output diagnostics all connections and configurations of the transmitter must be enabled to avoid any da...

Page 16: ...rate 5 V 3 3 Simulates 100 of the output range On the range 0 10V the transmitter will generate 10 V If the deviations are too large 0 05V or 0 05mA between the signal issued and the value displayed on the multimeter we recommend that you return the transmitter to our factory For the diagnostic of the channel 2 go to F 313 folder and perform the same procedure as for the channel 1 For the diagnost...

Page 17: ...larms F400 folder corresponds to the alarm 1 setting F410 folder corresponds to the alarm 2 setting F420 folder corresponds to the alarm 3 setting The alarm setting procedure explained below corresponds to the alarm 1 setting For the alarms 2 and 3 settings go to the corresponding folder and perform the same procedure as for the alarm 1 The transmitter is powered on Press OK Enter the activation c...

Page 18: ...Press Up key to go to F404 folder F414 for alarm 2 and F424 for alarm 3 then press OK This folder is about the delay time 1 setting Set the delay time 1 with Up and Down keys Press OK when the last digit has been set F404 blinks Press Up key to go to F405 folder F415 for alarm 2 and F425 for alarm 3 then press OK This folder is about the delay time 2 setting Set the delay time 2 with Up and Down k...

Page 19: ...18 for the alarm 2 and F428 for the alarm 3 then press OK Select ON to activate the alarm latching or OFF to deactivate it Press OK F400 Manage the alarms 19 Delay time 10 min Acknowledgement Alarm ON Alarm OFF Acknowledgement Acknowledgement LED ON LED OFF Latching ON m t Threshold 1 Threshold 2 Acknowledgement Alarm ON Alarm OFF Delay time 10 min Acknowledgement LED ON LED OFF Latching OFF m t T...

Page 20: ... S 0 1000 Pa Current measurement 120 Pa New measurement 125 Pa The pressure source being stable the user selects a low integration Integration 1 maximum admitted variation 10 Pa The variation is lower than 10 Pa it is possible to apply the integration calculation formula Next displayed value 9 125 1 120 10 124 5 i e 124 Pa If the new measurement had been de 131 Pa the next displayed value would ha...

Page 21: ...edure as for the channel 1 To add a gain to the channel 3 go to F 540 folder and perform the same procedure as for the channel 1 8 5 Add an offset In order to compensate any possible drift of the sensor it is possible to add an offset to the value displayed by the transmitter entering a digital value via the keypad The transmitter is powered on Press OK Enter the activation code see page 9 Press O...

Page 22: ...or board Probe board deactivated F 201 Enumeration 2000 Unit selection of the channel 1 According to probe and board F 210 Enumeration 2110 Selection of probe or board Probe board deactivated F 211 Enumeration 2100 Unit selection of the channel 2 According to probe and board F 220 Enumeration 2210 Selection of probe or board Probe board deactivated F 221 Enumeration 2200 Unit selection of the chan...

Page 23: ... current Generation according to the output signal 0 10 V 0 5 V 0 20 mA 4 20 mA 0 V 0 V 0 mA 4 mA 5 V 2 5 V 10 mA 12 mA 10 V 5 V 20 mA 20 mA 9 4 F 400 manage the alarms Code Register type Modbus Description Possibilities F 400 Enumeration 4000 Alarm mode of the alarm 1 1 None 2 Rising edge 3 Falling edge 4 Monitoring F 401 U8 4010 Channel selection alarm 1 Channel 1 Channel 2 Channel 3 F 402 Real ...

Page 24: ...4210 Channel selection alarm 3 Channel 1 Channel 2 Channel 3 F 422 Real 4220 Threshold 1 setting of the alarm 3 According to the connected probe F 423 Real 4230 Threshold 2 setting or hysteresis of the alarm 3 According to the connected probe F 424 U16 4240 Delay time 1 setting of the alarm 3 From 0 to 600 s F 425 U16 4250 Delay time 2 setting of the alarm 3 From 0 to 600 s F 426 Boolean 4280 Audi...

Page 25: ...30 Real 5300 Channel 2 coefficient From 0 01 to 5 F 540 Real 5400 Channel 3 coefficient From 0 01 to 5 F 521 Real 5210 Channel 1 offset According to probe F 531 Real 5310 Channel 2 offset According to probe F 541 Real 5410 Channel 3 offset According to probe Functions recap and Modbus connections 25 ...

Page 26: ......

Page 27: ......

Page 28: ...NTang transmitter_CPE310 S CPE311 S 24 07 17 RCS 24 Périgueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products ...