7. F 400: MANAGE THE RELAYS
When the transmitter is still in alarm state, the relay goes off and activates its negative or positive security according to its
configuration.
Three relays activation modes are available:
•
Rising edge (1 threshold):
the relay goes off when the measurement
exceeds
the threshold and stops when it
is
below
the threshold.
•
Falling edge (1 threshold):
the relay goes off when the measurement is
below
the threshold and stops when it
exceeds
the threshold.
•
Monitoring (2 thresholds):
the relay goes off when the measurement is outside the defined low and high
thresholds.
It is possible to set 2 different relays activation:
•
“F 400”
folder corresponds to the
relay 1
setting
•
“F 410”
folder corresponds to the
relay 2
setting
The relay setting procedure explained below corresponds to the relay 1 setting. For the relay 2 setting, go to the
corresponding folder and perform the same procedure as for the relay 1.
The transmitter is powered on.
➢
Press
OK
.
➢
Enter the activation
code (see page 8).
➢
Press
OK
.
➢
Press the
Up
key to go to the
“F 400”
folder.
➢
Press
OK
.
This folder corresponds to the activation relay mode.
➢
With
Up
and
Down
keys, select the required relay activation mode:
16
F 400: MANAGE THE RELAYS
Rising edge
Falling edge
Measurement (m) > Threshold (S) during the time-delay
T1 Relay activation
→
Measurement (m) < Threshold (S) - Hysteresis (H)
during the time-delay T2 Relay deactivation
→
Measurement (m) < Threshold (S) during time-delay
T1 Relay activation.
→
Measurement (m) > Threshold (S) + Hysteresis (H)
during time-delay T2 Relay deactivation
→
Monitoring
The relay goes off when the measurement is outside the low and
high thresholds.