Centauri Energy Server
–
User Manual
Model Number - GF-20000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
22
1)
The Energy Server must be installed in clean and dry room (the environment temperature
within 0 ~ 40
o
C, the relative humidity of 5% ~ 90%, and the optimal operating temperature of 25
o
C).
If the room temperature is 40
o
C, the indoor exhaust fan should be installed to ensure sufficient air
flow in the room so that the equipment gets full heat dissipation in case of the rise in room
temperature. It is best to be equipped with A/C system.
2)
To facilitate the wiring daily maintenance, diagnosis, and repair of the Energy Server, please
make sure that the safe space of the front and the back doors is reserved (The advisable space is 1000
mm or more to ensure that the door of the Energy Server can be fully opened, and the operators can
pass the door freely).
Fig 5 Schematic Diagram of System Installation
i.
For altitude greater than 1000 meters, the derating of the Energy Server should be used.
ii.
The bearing capability of the pallet should be greater than the equipment weight (The
equipment weight is as shown in the technical specifications).
4.5 Cabinet Handling:
First of all, remove the surrounding rat proof baffles below the machine, and then get the mechanical
arms of the special handling equipment (hoisting equipment, stackers or forklift) with the sufficient