Sirius Capacitor Module
–
User Manual
Model Number - 3550-48-B-1.7C-M-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
23
•
Recommended Charger for Recovery:
Maximum Current
10 A
Recommended Voltage
44V-54V
6.
Connecting the Module in Parallel or in Series:
The capacity or voltage of the Module can be increased by connecting them in Parallel or Series
combination respectively.
6.1 Parallel Connection of Sirius Modules:
Any number of Modules can be connected in parallel.
•
Steps to Connect Modules in Parallel:
Refer to the parallel combination of the Sirius Modules as shown below and make your connection
accordingly.
•
Connect the
positive (+)
of the
F12 Terminal
of all Modules.
Caution!
Do not use more than 10A to recover the Module.