CENTAURI ENERGY SERVER
User Manual - Model 30-2017/12/18-VERSION 1.0
11
o
The display screen supports two control modes, namely the button control and touch
control. The system default state is in the touch screen input mode, the corresponding
operations are available through clicking the icon on the LCD screen.
o
Click the "
" button on the any interface to switch to the button control mode,
and then press the "
" button to return to the touch screen control mode.
o
After clicking "
" button, the user can move the cursor through pressing "
"
or "
" button to choose the required control button and then press the "
" button
for confirmation.
1.5.2.2
Description of Function Buttons
Button Symbols
Name
Functions
INV ON
ON button
When you press this button, the system executes the boot
command and then runs after pressing the “OK” button.
When you press this button, the system executes the
INV OFF
OFF button
shutdown command and the shutdown operation is
initiated by pressing the “OK” button. At this moment, the
system and output shut down.
SILENCE ON/OFF
Beep ON/OFF
The system alarm is cancelled by this button press and the
system alarm is activated by pressing this button again.
FAULT CLEAR
Clear the system
Press this button to clear executed abnormal protection
fault
command, the system will restart and run.
EPO
Emergency stop
When the button is pressed, the system immediately shuts
the power supply.
Table 6 Description of Function Buttons
1.5.3 Introduction to Input Breaker
Signs
Name
Function
DC START
DC start switch
When the switch is dialed, the system performs the battery
soft start.
MANUAL
Manual bypass
This switch may only be operated by authorized staff. The
load is connected directly to the bypass input by switching on
BYPASS
switch
this button.
OUTPUT
Output switch
Dial the switch to switch on the connection between the load
and the system static switch.
BYPASS
Bypass switch
Dial the switch to switch on the bypass AC input.
RECTIFIER
Rectifier switch
Dial the switch to switch on the rectifier AC input.
PV 1#
PV 1# input switch
When the switch is enabled, the system
MPPT 1# will supply the power.
PV 2#
PV 2# input switch
When the switch is enabled, the system
MPPT 2# will supply the power.
PV 3#
PV 3# input switch
When the switch is enabled, the system
MPPT 3# will supply the power.
PV 4#
PV 4# input switch
When the switch is enabled, the system
MPPT 4# will supply the power.
Table 7 Introduction to Input Air Switch