86
User’s Manual
PMX_MULTI
Specifications
Output
PMX32-3DU
PMX32-3TR
PMX32-2QU
Rating
Output voltage CH1
32.000 V
32.000 V
32.000 V
CH2
32.000 V
32.000 V
32.000 V
CH3
—
6.000 V
18.000 V
CH4
—
—
18.000 V
Output current CH1
3.000 A
3.000 A
2.000 A
CH2
3.000 A
3.000 A
2.000 A
CH3
—
5.000 A
2.500 A
CH4
—
—
2.500 A
Constant
voltage
Maximum
voltage setting
CH1
33.600 V
33.600 V
33.600 V
CH2
33.600 V
33.600 V
33.600 V
CH3
—
6.300 V
18.900 V
CH4
—
—
18.900 V
Resolution
1 mV
Voltage setting accuracy
*1
±(0.03 % set +5 mV)
Input line
regulation
*2
CH1
3 mV
3 mV
3 mV
CH2
3 mV
3 mV
3 mV
CH3
—
1 mV
1 mV
CH4
—
—
1 mV
Load regula-
tion
*3
CH1
4 mV
4 mV
2 mV
CH2
4 mV
4 mV
2 mV
CH3
—
5 mV
3 mV
CH4
—
—
3 mV
Transient response
*4
50 μs
Ripple noise (rms)
*5
500 μV
Command delay
80 ms
Rise time (at rated load)
*6
10 ms ±30 %
Fall time
(at no load)
*7
CH1
350 ms ±30 %
350 ms ±30 %
350 ms ±30 %
CH2
350 ms ±30 %
350 ms ±30 %
350 ms ±30 %
CH3
—
220 ms ±30 %
240 ms ±30 %
CH4
—
—
240 ms ±30 %
Temperature coefficient
(TYP)
100 ppm/ °C