Product Description

Z45FK, Z46FK, Z47FK, Z60FK

L

Page 6 / 8

2.90-20.060-01-EN | 2022-10-05

Cable connection

 Disconnect unit from power supply.

 Strip the insulation from 10 mm of the wire. Cross-sectional area of 

connection:
Solid wire 0.08 .. 2.5 mm²
Litz wire without conductor end sleeve 0.08 .. 2.5 mm² Litz wire with conductor 
end sleeve 0.5 .. 1.5 mm²
Solid wires and litz wires with conductor end sleeves can be inserted into the 
spring terminals (1) directly. Insert the wire straight and press it in until the wire 
will not go any further and it clicks into place in the spring terminal.
In the case of litz wires without conductor end sleeves, the spring terminal must 
be opened using a slotted screwdriver. Insert the screwdriver into the test 
socket (2) under the contact in order to open it, insert the litz wire straight, and 
then remove the screwdriver.

"Terminal slot (3) for Z43 connecting bridge.

"Device connection - see wiring diagram.

Removing a Wire

Insert a slotted screwdriver (max. blade width 3 mm) into the 
test socket (2) under the contact to open the spring 
terminal (1), then remove the wire.

Removing the Module from the Standard Rail

Gently press in the spring under the module with a slotted 
screwdriver and remove the module upward.

1

3

2

Summary of Contents for Z45FK

Page 1: ...are fitted with spring terminals which make it possible to connect wires quickly and easily It is not necessary to use a tool to connect solid wires and litz wires with conductor end sleeves an ordina...

Page 2: ...mmissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recogn...

Page 3: ...es Z46FK 2 000 000 switching cycles Display LED operating display Manual switch Z45FK Z46FK None Z47FK Manual switch at field level Z60FK Manual switch at field level with a poten tial free feedback c...

Page 4: ...05 Dimensions Connection ZxxFK Z43 250 V AC 6 A 1500 VA 11 A1 14 12 GN A2 Z45FK 14 24 12 22 11 A1 21 230 VAC 0 25 A 60 VA GN A2 Z46FK A1 A3 0 ON A3 AUTO OFF 11 A1 12 14 250 V AC 6 A 1500 VA GN A2 Z47F...

Page 5: ...c installation can cause death due to electric shock Mounting removal may only be carried out when power is switched off Comply with VDE guidelines and local wiring regulations when mounting removing...

Page 6: ...any further and it clicks into place in the spring terminal In the case of litz wires without conductor end sleeves the spring terminal must be opened using a slotted screwdriver Insert the screwdrive...

Page 7: ...oper place to make the cut Then insert the connecting bridge Z43 from the top or from the bottom into the contact slot and press it down WARNING Contact with live components of the building s electric...

Page 8: ...are switched at the output terminals In secondary earthed systems PELV this prevents any unwanted connection to ground or the reference potential and prevents an active signal from being generated at...