Datasheet 2.50-40.151-11-EN
SBM51/11
Product Description
Issue 2014-11-19
Assignment of Software Menus / System Objects to the Energy Monitoring Devices
Parameter Settings for the Energy Monitoring Devices
Parameter 2209 "External building complex malfunction"
Parameter 2209 shows the status of a device for the menu group.
DDC4000: Active parameter in system object H000.xx.
■
"0"
Device present
■
"1"
Device not present
Parameter 2215 (totals menu) - Adjustment frequency
Parameter 2215 shows the adjustment frequency. Possible display values are:
■
16 2/3 Hz (displayed as 16)
■
50 Hz
■
60 Hz
■
400 Hz
Parameter 2215 is only available for energy monitoring devices A230/A230s.
Parameter 2220 (totals menu) - Set display of performance values (parameters 2254, 2255,
2256)
Parameter 2220 sets the display of the performance values for parameters 2254, 2255, 2256 within
the software menu group.
■
"deleted" (--) or "0"
Energy in kWh, kVAh, kVArh
■
"1"
Energy in Wh, VAh, VArh
Parameter 2245 (totals menu) - Set display of energy values
Parameter 2245 sets the display of the energy values for parameters 2212, 2251, 2215 and 2252
(phase menu L1 and L2) within the software menu group.
■
"deleted" (--) or "0"
Performance in kW, kVA, kVAr
■
"1"
Performance in W, VA, VAr
Energy moni-
toring device
Phase
DDC3000
DDC4000
Software menu
M090 SBM 51
System object
"H000"
1
1
1
H000.01
2
2
H000.02
3
3
H000.03
Totals menu
4
H000.04
2
1
5
H000.05
2
6
H000.06
3
7
H000.07
Totals menu
8
H000.08
...
Repeating
Consecutive
Consecutive
8
1
29
H000.29
2
30
H000.30
3
31
H000.31
Totals menu
32
H000.32