background image

A

Page 5 / 16

Datasheet 2.50-40.151-11-EN

SBM51/11

Product Description

Issue 2014-11-19

When connecting the third-party devices, use a cable of at least type JY(St)Y 2x2x0.8 Lg: two leads 
stranded into a pair, with plastic insulation and an electrostatic shield with a lead diameter of at least 
0.8 mm. Use a stranded pair of leads for the data lines (+ and -). 
The maximum cable length for the Modbus is 1000 m.
The SBM51/11 uses the following interface parameters:

Baud rate: 9600 baud 

Data bits: 8 

Stop bit: 1 

Parity: even 

The energy monitoring devices must use the same settings. These parameters can be entered 
directly on the energy monitoring device.

Mounting

!

CAUTION

Switching on the power supply of unparameterized products can lead to unforeseen consequences 
such as malfunctions or material damage.
Switch on the power only after the device has been configured by the commissioning technician.

Removal

TH 35-7.5

1

2

3

4

1

2

3

4

5

Summary of Contents for SBM51/11

Page 1: ...220 and A230 A230s with communication module EMMOD 201 from the company Camille Bauer Application The switch cabinet bus module SBM51 11 is used to integrate up to 8 energy monitoring devices into the...

Page 2: ...to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with t...

Page 3: ...tors and controls 2 LEDs in housing 2 rotary switches in housing for setting the switch cabinet bus address Interfaces Switch cabinet bus to DDC system Serial interface RS485 bus Modbus RTU Overvoltag...

Page 4: ...the switch cabinet bus also applies to the CAN bus Switch cabinet bus When connecting the switch cabinet bus use a cable of at least type JY St Y 2x2x0 8 Lg two x two leads stranded into a pair plast...

Page 5: ...m cable length for the Modbus is 1000 m The SBM51 11 uses the following interface parameters Baud rate 9600 baud Data bits 8 Stop bit 1 Parity even The energy monitoring devices must use the same sett...

Page 6: ...of the DDC controller is described in the respective project planning documentation Indicators and Controls 1 Rotary switch for setting the switch cabinet bus address 2 Switch cabinet bus LED LED Sign...

Page 7: ...tting the switch cabinet bus address are located inside the SBM51 11 Set the first rotary switch to the first digit of the switch cabinet bus address and the second rotary switch to the second digit T...

Page 8: ...eter 2204 Foreign bus OK Parameter 2204 reports malfunctions on Modbus to the SBM51 11 1 Modbus is working without errors 0 Errors occurred on Modbus Parameter List in the DDC4000 System Enable parame...

Page 9: ...0 A230s Parameter 2220 totals menu Set display of performance values parameters 2254 2255 2256 Parameter 2220 sets the display of the performance values for parameters 2254 2255 2256 within the softwa...

Page 10: ...the digital input on the energy monitoring device The rate that currently applies is displayed in parameter 2225 totals menu If the digital input on the energy monitoring device is used for changing...

Page 11: ...value 1 Delta voltage U12 V 2211 Analog actual value 2 Phase voltage U1 V 2212 Analog actual value 3 Total energy incoming high rate k Wh 2251 Analog actual value 4 Total energy incoming low rate k Wh...

Page 12: ...lue 3 Total reactive energy inductive incoming high rate k VArh 2251 Analog actual value 4 Total reactive energy inductive incoming low rate k VArh 2215 Analog actual value 5 Total reactive energy cap...

Page 13: ...er name Parameter plain text Parameters provided Operating mode L1 L2 L3 Unit 2209 External building com plex malfunction Participant is logged in 2210 Analog actual value 1 Module type 2211 Analog ac...

Page 14: ...deleted or 0 off 1 on 2220 Q digital setpoint 2 Factor for display Power unit 2245 Q digital setpoint 3 Factor for display Energy unit 2246 Q digital setpoint 4 0 high rate 1 low rate 2217 Operating m...

Page 15: ...t Present 2251 Total power incoming low rate Present Present Present 2215 Total power outgoing high rate Present Present Present 2252 Total power outgoing low rate Present Present Present 2253 Phase c...

Page 16: ...Present 2255 Apparent power S3 Present 2256 Idle power Q3 Present 2257 Power factor cos 3 Present Par no Measured quantity Single phase 3W balanced load 4W balanced load 3W unbalanced load 4W unbalanc...

Reviews: