- Connection of several input/output modules via CAN bus

NOTE

The terminal block terminal “17” through terminal “20” (feed-through terminals) can be inserted and 
disconnected without interruption.

Installation

!

CAUTION

This product description contains the specific settings and functions of the input/output module. In 
addition to these instructions, the product descriptions of other system components, such as the 
DDC4000e automation station, are to be observed.

!

CAUTION

Switching on the power supply of unparameterized products can lead to unforeseen consequences 
such as malfunctions or material damage.
Switch on the power only after the device has been configured by the commissioning technician.

NOTE

The input/output module can be connected to an existing fieldbus or switch cabinet bus.
Further information can be found in the DDC4000 project planning documentation

Switch cabinet bus

When connecting the switch cabinet bus, use a cable of at least type JY(St)Y 2x2x0.8 Lg: two x two 
leads stranded into a pair, plastic insulation and an electrostatic shield with a lead diameter of at least 
0.8 mm. Use a stranded pair of leads for the data lines (+ and -) and another free lead for the 
ground (0).
At the end of the switch cabinet bus (farthest point from the DDC controller), install a terminating 
resistor of about 180 ohms between both data lines (+ and -). The terminating resistor is included with 
the DDC controller
The maximum cable length for the switch cabinet bus is 200 m.

17

18

18

17

19

20

20

19

BMA0804

17

18

18

17

19

20

20

19

BMA0804

17

18

18

17

19

20

20

19

BMD1204

12..24V=

0V

Can+

Can-

01

02

03

Summary of Contents for BMA0804

Page 1: ...log outputs In manual mode the output signal can be set in 10 increments 0 100 0 2 10 V DC LED displays for the operating states of the inputs and outputs Communication is controlled via LED Label car...

Page 2: ...y with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the descri...

Page 3: ...displaying bus communication See chapter LED displays page 11 4 manual automatic rotary switches for automatic and manual operation of analog outputs 0 100 0 2 10 V DC Address switch Two rotary switc...

Page 4: ...re conductor 0 2 1 5 mm2 0 08 2 5 mm2 0 08 1 5 mm2 0 2 1 5 mm2 Conductor cross section fine wire conductor 0 25 1 5 mm2 0 08 2 5 mm2 0 08 1 5 mm2 0 25 1 5 mm2 Conductor cross section fine wire conduct...

Page 5: ...DDC4000e connection 44 7 0 0 9 60 0 143 5 19 20 17 18 19 20 17 18 83 82 81 86 85 84 88 87 93 92 91 96 95 94 98 97 CAN 12 24V Can Can 0V 53 52 51 GND 10V AI1 56 55 54 GND AI2 10V 59 58 57 GND AI3 10V...

Page 6: ...uctors CAUTION 3 wire and 4 wire applications may not be mixed AO1 AO4 24V 24V 0V 24V 0V Y AI1 AI8 24V 24V 0V 24V 0V A 0 10VDC KP10 GND NTC 500k AO1 AO4 24V 24V 0V 24V 0V Y GND 0V AI1 AI8 24V 24V 0V 2...

Page 7: ...by the commissioning technician NOTE The input output module can be connected to an existing fieldbus or switch cabinet bus Further information can be found in the DDC4000 project planning documentat...

Page 8: ...d and another free wire for the ground connection 0 At the end of the fieldbus furthest point from the DDC controller install a terminating resistor of about 180 ohms between both data lines and The t...

Page 9: ...ing to the sensor type table Setting range of the analog outputs 2 10V DC or 0 10 V DC Default value for the outputs in the event of bus failure or failure of the automation station NOTE Parameterizat...

Page 10: ...planning documentation Before switching on the supply voltage check the electric installation and the device connections After configuring the device and switching on the supply voltage check the func...

Page 11: ...hts up red LED status combination LED Meaning Cause off Module not in operation No operating voltage or operating voltage too low Yellow on green LED and red LED on Module in operation but there is a...

Page 12: ...Product Description BMA0804 J Page 12 12 2 60 80 804 01 EN 2019 01 17...

Reviews: