Product Description

BMA0804

J

Page 10 / 12

2.60-80.804-01-EN | 2019-01-17

NOTE

On delivery, the address “00” is set, which means:
- No bus communication
- No parameterization possible
- Manual operation is effective. The 4 analog outputs can be switched in 10% increments (0..10 V DC)
. In automatic rotary switch position, the output is 0 V DC.
- Sensor inputs in test mode

Commissioning

!

CAUTION

Commissioning by switching on the supply voltage may occur only after the commissioning 
technician/engineer has finished configuring the DDC and has set the bus address.

Configuration is described in the DDC controller project planning documentation. 

Before switching on the supply voltage, check the electric installation and the device connections.

After configuring the device and switching on the supply voltage, check the functions of the module 
and the connected inputs and outputs.

Functional test

It is possible to check the correct wiring and function of the inputs and outputs.

Set the bus address “00”.

The function and wiring of the 4 outputs 0..10 V DC can be tested with the manual/automatic rotary 
switch.

The correct polarity and wiring of the 8 AI1 through AI8 inputs can be checked with a diode and a 
resistor 180 

 (series connection).

Target display:
- Open contact: Red LED
- Resistance diode combination correctly poled: Green LED
Possible wiring errors:
- Open contact: Green LED
- Resistance diode combination connection: Red LED

Summary of Contents for BMA0804

Page 1: ...log outputs In manual mode the output signal can be set in 10 increments 0 100 0 2 10 V DC LED displays for the operating states of the inputs and outputs Communication is controlled via LED Label car...

Page 2: ...y with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the descri...

Page 3: ...displaying bus communication See chapter LED displays page 11 4 manual automatic rotary switches for automatic and manual operation of analog outputs 0 100 0 2 10 V DC Address switch Two rotary switc...

Page 4: ...re conductor 0 2 1 5 mm2 0 08 2 5 mm2 0 08 1 5 mm2 0 2 1 5 mm2 Conductor cross section fine wire conductor 0 25 1 5 mm2 0 08 2 5 mm2 0 08 1 5 mm2 0 25 1 5 mm2 Conductor cross section fine wire conduct...

Page 5: ...DDC4000e connection 44 7 0 0 9 60 0 143 5 19 20 17 18 19 20 17 18 83 82 81 86 85 84 88 87 93 92 91 96 95 94 98 97 CAN 12 24V Can Can 0V 53 52 51 GND 10V AI1 56 55 54 GND AI2 10V 59 58 57 GND AI3 10V...

Page 6: ...uctors CAUTION 3 wire and 4 wire applications may not be mixed AO1 AO4 24V 24V 0V 24V 0V Y AI1 AI8 24V 24V 0V 24V 0V A 0 10VDC KP10 GND NTC 500k AO1 AO4 24V 24V 0V 24V 0V Y GND 0V AI1 AI8 24V 24V 0V 2...

Page 7: ...by the commissioning technician NOTE The input output module can be connected to an existing fieldbus or switch cabinet bus Further information can be found in the DDC4000 project planning documentat...

Page 8: ...d and another free wire for the ground connection 0 At the end of the fieldbus furthest point from the DDC controller install a terminating resistor of about 180 ohms between both data lines and The t...

Page 9: ...ing to the sensor type table Setting range of the analog outputs 2 10V DC or 0 10 V DC Default value for the outputs in the event of bus failure or failure of the automation station NOTE Parameterizat...

Page 10: ...planning documentation Before switching on the supply voltage check the electric installation and the device connections After configuring the device and switching on the supply voltage check the func...

Page 11: ...hts up red LED status combination LED Meaning Cause off Module not in operation No operating voltage or operating voltage too low Yellow on green LED and red LED on Module in operation but there is a...