USER GUIDE

TM0098

WARNING

Please read this guide fully before attempting to operate the unit.

1.0 Introduction

This Guide describes the use of the Kidde Fire Protection Hot Wire Test Box (part number 1-53836-
K237) to test aspirating smoke detection systems.  The unit provides 6V AC output from 220-240V AC
mains supply.  High current at low voltage is passed through a cable in order to heat it, which causes
its insulation to burn giving off smoke.  A timer is incorporated to provide a selectable burn period of
up to 3 minutes. The timer also helps to prevent the unit being inadvertently left on for an extended
period.  The unit 

must never

 be left on unattended.

The unit must be operated for 

no more than three (3) minutes 

continuously and must be left off

immediately after operating for a 

 period of at least six (6) minutes to allow it to cool.

The unit is protected against over-temperatures by a thermal switch.  Once tripped, the thermal switch
will not allow operation for an extended period (up to an hour) regardless of power being present or
not.  The thermal switch cannot be by-passed or reset manually.

Summary of Contents for TM0098

Page 1: ...rn giving off smoke A timer is incorporated to provide a selectable burn period of up to 3 minutes The timer also helps to prevent the unit being inadvertently left on for an extended period The unit must never be left on unattended The unit must be operated for no more than three 3 minutes continuously and must be left off immediately after operating for a period of at least six 6 minutes to allo...

Page 2: ... a 15 minute period unless they are directly exposed to the smoke plume It is strongly recommended that personnel wear appropriate protective equipment such as an E1 respirator conforming to EN140 and goggles without ventilation conforming to EN166 in the following situations Multiple tests are required Personnel are within the immediate vicinity e g 2m of the smoke source Due to the nature of hot...

Page 3: ...ed and cut to the required length The ends should be stripped at approximately 15mm using a suitable tool If in doubt please seek guidance from a qualified electrician Only use the recommended test wire Under no circumstances should test wires be shorter than 60cm or 2x1m in parallel This is likely to age or blow the inlet fuse and may cause damage to the unit Ensure that no power is connected to ...

Page 4: ...on website at www bfpsa org uk 8 Specifications Hot Wire Test Box Part Number 1 53836 K237 Voltage Input 220 240V AC 50Hz Input Rating 1 6A 240V AC 50Hz Fuse 220 240V AC T Anti surge 1 6A Output 6V AC nominal 20A Operating Time Maximum on time 3 minutes 180 seconds Minimum off time between tests 6 minutes 360 seconds Ingress Protection IP 30 Indoor use only This product is not to be used in the pr...

Reviews: