© 2018 United Technologies Corporation 

1 / 2 

P/N 3102467-

EN • REV 003 • 04JUN18 

 

KI-HRD Intelligent Fixed-
Temperature and Rate-of-Rise 
Heat Detector Installation Sheet 

 

Description 

The model KI-HRD Intelligent Fixed-Temperature and Rate-of-Rise 
Heat Detector is an intelligent device that contains a rate-of-rise and 
fixed-temperature heat sensor function to detect fire. The heat sensor 
monitors the temperature of the surrounding air and the detector 
analyzes the data from the sensor to determine whether to initiate an 
alarm. The rate-of-rise heat function quickly detects a fast, flaming fire. 
The fixed-temperature heat function detects fire when the air 
temperature near the detector exceeds the alarm point. 

LED indicator. 

The LED indicator (see Figure 1) displays the following 

states: 

• 

Normal: Green LED indicator flashes, no action. 

• 

Alarm/active: Red LED indicator flashes, evacuate the area. 

Installation 

Notes 

• 

This detector does not operate without electrical power. As fires 
frequently cause power interruption, discuss further safeguards 
with the local fire protection specialist. 

• 

This detector does not sense fires in areas where heat cannot 
reach the detector. Heat from fires in walls, roofs, or on the 
opposite side of closed doors may not reach the detector. 

• 

This heat detector by itself does not provide life safety protection. 
Use this detector in conjunction with ionization or photoelectric 
smoke detectors, or both for life safety situations. 

• 

This detector does not detect oxygen levels, smoke, toxic gases, 
or flames. Use this device as part of a broad-based life safety 
program which includes a variety of information sources pertaining 
to heat and smoke levels, extinguishment systems, visual and 
audible devices, and other safety measures. 

• 

Independent studies indicate that heat detectors should only be 
used when property protection alone is involved. Never rely on 
heat detectors as the sole means of fire protection. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 

The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

In Canada, install according to CAN/ULC-S524 

Standard for the 

Installation of Fire Alarm Systems,

 CSA

 

C22.1 

Canadian Electrical 

Code

, and the local authority having jurisdiction. 

To install the device: 

1.  Install and wire the base, as described on the installation sheet 

supplied with the base. 

2.  Remove the serial number label from the detector and attach it to 

the project documentation. 

3.  Attach the detector to the base by rotating the detector clockwise 

until it snaps into the locked position. 

Figure 1: KI-HRD features 

 

 
(1)  Self-locking tab  
(2)  LED indicator 

 

 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

Caution: 

Heat damage. Excessive heat may damage the detector 

outer cover. Do not apply excessive heat when using a hair dryer. 
When using a Testifire detector tester, you must install a Testifire 
Adapter Assembly. 

Make sure the Testifire Adapter Assembly (model K-TSTSPACER) is 
installed in the Testifire detector tester before testing. Refer to the 

Testifire Adapter Assembly Installation Sheet

 (P/N 3102495-ML) for 

further details. 

To perform an initial installation test: 

1.  Visually inspect each detector and verify that it is installed in the 

correct location. Make sure it is not adversely affected by factors 
not apparent on the plans. 

2.  Remove the detector from its base and verify that the proper 

detector address, trouble signals, and messages are reported. 

3.  If wired for Class A operation, verify that the detector continues to 

operate first with the SLC_IN disconnected, and then with the 
SLC_OUT disconnected. (Refer to the installation sheet for the 
base.) 

4.  Place a momentary ground fault on the SLC circuit to verify 

operation of the ground fault detection circuitry. 

5.  Perform a sensor function test, as described below. 

(1)

(2)