Kidde FX-2WIRE Installation Sheet Download Page 1

 

© 2020 Carrier 

1 / 2 

P/N 3101082-EN • REV 006 • ISS 20OCT20 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX-2WIRE Analog Class A-B 

Two-Wire Module Installation 

Sheet 

Operation 

The FX-2WIRE module is designed to interface between compatible 

conventional two-wire smoke detectors and a control panel. It monitors 

the circuit and smoke detectors and signals the control panel of any 

trouble or alarm conditions. The module also regulates and supervises 

the 24 VDC input power. 
The module is configured from the factory to operate as a two-wire 

alarm device that does not require alarm verification. It can be 

configured for two-wire alarm verified operation through front panel 

programming or the configuration utility. When using the alarm 

verification feature of the control panel, do not mix normally open 

contact initiating devices with two-wire conventional smoke detectors. 
The module recognizes the CleanMe signal from detectors that 

support this feature. 
The module device address is set using the two rotary switches 

located on the front of the module. One device address is required. 
The device can be set for Class B or Class A operation using the slide 

switch located on the front of the module. 

Caution: 

This module cannot be used on a device loop with isolator 

modules or isolator bases. 

Slide switch operation 

The following slide switch settings determine the operation of the 

module. Setting the initial slide switch position is generally performed 

during module installation. This setting can be changed while the 

system is operating, but the change must be confirmed through front 

panel programming or using the configuration utility. 

Table 1: Slide switch operation 
Setting   Operation   Device type description [1] 

1  

Class B 

Class B 2-wire smoke non-verified: 

Configures the module to monitor two-wire 

conventional smoke detectors (that do not 

require alarm verification) and normally 

open contact initiating devices on a Class B 

circuit. 

Not used 

 

Class A 

Class A 2-wire smoke non-verified: 

Configures the module to monitor two-wire 

conventional smoke detectors (that do not 

require alarm verification) and normally 

open contact initiating devices on a Class A 

circuit. 

[1] Additional device types are available through front panel 

programming or the configuration utility. Refer to applicable control 

panel technical reference manual. 

Figure 1: Slide switch 

 

LED operation 

The module provides a bicolor LED that shows its status. 
Normal: Green LED flashes 
Alarm/active: Red LED flashes 

Installation 

Install and wire this device in accordance with applicable national and 

local codes, ordinances, and regulations. 

WARNING: 

This module will not operate without electrical power. As 

fires frequently cause power interruption, you should discuss further 

safeguards with your local fire protection specialist. 

Note: 

The module is shipped from the factory as an assembled unit; it 

contains no user-serviceable parts and should not be disassembled. 

To install the module: 

1.  Verify that all field wiring is free of opens, shorts, and ground 

faults. 

2.  Make all wiring connections as shown in “Wiring” and in Figure 4. 
3.  Set the module address. Refer to the panel technical reference 

manual for a list of valid addresses. 
Use a screwdriver to adjust the two rotary switches on the front of 

the module. Set the TENS rotary switch (0 through 12) for the 10s 

and 100s digit and the ONES rotary switch for the 0 through 9 

digit. For example: device address 21, set TENS rotary switch to 2 

and set the ONES rotary switch to 1 (see Figure 2). 

4.  Set slide switch P1 to appropriate setting. Refer to “Operation.” 
5.  Mount the module on the electrical box using screws provided with 

the electrical box. 

6.  Mount the wall plate on the module using the hardware shown in 

Figure 3. 

Figure 2: Module address 

 

(1) Insert screwdriver here 
 

TB1

TENS

ONES

TB2

12

11

10

9

4

3

2

1 0

8

5 6 7

0 9

1

8

2

7

3

6

4 5

P1

1

3

2

(1)

-