Effective: January 2017

K-76-227

®

Hand-Held Device Programmer

For SmartOne

®

 Devices and DS Series Detectors

DESCRIPTION

The Hand-Held Device Programmer (the “Programmer”) pro-
vides the system installer/service person with a convenient
means to assign device address information and test device
operation. The Programmer is designed to support all Smar-
tOne intelligent/addressable devices and DS Series Detectors
(adapter base included).

Note:

Prior to using the Programmer, ensure that you have 
the following supplied accessories:

SLC Interface Adaptor

AC Adaptor (120V)

AI/AO Module Adaptor

4 NiMH Rechargeable AA Batteries

Storage Case

OPERATION OVERVIEW

To turn the Programmer on:
1.

Press the button labeled “ON.”

2.

Verify that the green “

Status

” LED is lit, and the LCD dis-

play message reads “

SLC Programmer

.”

After approximately 4 seconds, the LCD display should
show the first Main Menu level option, “

Single Address-

ing

.”

To turn the Programmer off:
From the Main Menu, press 

<

>

 or 

<

>

 until the LCD display

reads “

Power Off

”; then press 

<

 

E

 

>

 

(Enter)

, and the Program-

mer will turn off.
If you leave the Programmer idle, the Automatic Power Off fea-
ture will turn the Programmer off after the pre-set default time of
5 minutes. You can adjust the Power Off time to between 1 and
10 minutes.

FEATURES

Single or sequential device addressing modes

Compact design; user-friendly

AC and battery power operation

Adjustable LCD Contrast

Integral detector base: photo, ion, thermal detectors

Adapter Base for DS Series Detectors included

Snap-in AI/AO Module Adapter for easy changeover

SLC Interface Adapter Connector—no SLC wiring

No wiring or End-of-Line resistors required (except
NC AIs)

Less than 15 seconds addressing time per device

ON”

Button

Status LED

“Charging”

LED

Keypad
Buttons

LCD
Display

Summary of Contents for SmartOne K-76-227

Page 1: ...ads SLC Programmer After approximately 4 seconds the LCD display should show the first Main Menu level option Single Address ing To turn the Programmer off From the Main Menu press or until the LCD display reads Power Off then press E Enter and the Program mer will turn off If you leave the Programmer idle the Automatic Power Off fea ture will turn the Programmer off after the pre set default time...

Page 2: ...s show current firmware ver sion adjust the Power Off timer CONNECTING TO VARIOUS SMARTONE DEVICES The power may be ON or OFF when connecting the various SmartOne devices Smoke Heat Detectors Snap the detector into the detector base orient the index marker on the device to the five o clock position then rotate clockwise Addressable Input Addressable Output Modules 1 Connect the AI AO Module Adapto...

Page 3: ...ct Input Device P N 70 407008 002 requires that input terminal blocks SWA and SWB be jumpered together before addressing Unassigned Type In Alarm In Pre Alarm Contact Failure Drift Error Relay Fault Memory Fault Alarm Fault Device Test Mode Internal fault on device being tested Remove the device and allow the Programmer to clear Then re attach the device being tested If the device fails again do n...

Page 4: ...08 881 2000 www kiddefiresystems com This document does not contain any export controlled technical data SmartOne is a registered trademark of Kidde Fenwal Inc All other trademarks are the property of their respective owners SLC Out Adapter Connector SLC Interface Adaptor Jack Plug DS Series Detector Programming Adapter DS Series Detector CONNECTING TO DS SERIES DETECTORS A fixture that allows DS ...

Reviews: