K-1
August 1999
76-100016-001
Intelligent Suppression Control/Fire Alarm System
PEGAsys
APPENDIX K
ADDRESSABLE SIGNAL/SOUNDER MODULE
K-1
INTRODUCTION
The SmartOne™ Addressable Signal/Sounder Module (ASM) is
an intelligent field device that contains its own microprocessor,
4K of memory, and all necessary electronics to provide standard
notification or audio output. Connection is via the SmartOne
TM
com-
patible control panel’s power/communication line. This compo-
nent is a UL Listed
field device.
The ASM can be individually field programmed via hardware to
support notification appliances and NFPA Style Y (Class B) or
Style Z (Class A) operation. See Figure K-2 for audio/auxiliary
notification appliance switch and jumper selections, and NFPA
operation Style Y/Z terminal selections.
NOTE:
The ASM is not intended to be used as a releasing device
and is not compatible with solenoids or squibs.
For installation details and complete electrical and mechanical
specifications, see the ASM Installation Data Sheet (P/N 06-
235717-001).
A B
B
A
-
+
-
+
+ - - +
KIDDE-FENWAL, INC.
KIDDE-FENWAL, INC.
ASHLAND, MA 01721 U.S.A.
ASHLAND, MA 01721 U.S.A.
CAT. NO. 70-200200-001
CAT. NO. 70-200200-001
INSTRUCTIONS P/N 06-235717-001
INSTRUCTIONS P/N 06-235717-001
ALL OTHERS - POWER LIMITED
ALL OTHERS - POWER LIMITED
DEVICE
ADDRESS #
ADDRESS # _ _ _ _
_ _ _ _
AUX./AUDIO MODE
AUX./AUDIO MODE
SETTINGS
PC LINE TERMINALS - POWER LIMITED
PC LINE TERMINALS - POWER LIMITED
ADDRESSABLE SIGNAL/SOUNDER MODULE (ASM)
ADDRESSABLE SIGNAL/SOUNDER MODULE (ASM)
_ _ _ _
_ _ _ _
INSTRUCTIONS P/N 06-235717-001
INSTRUCTIONS P/N 06-235717-001
ADDRESS #
ADDRESS #
SETTINGS
AUDIO
P1=1&2
MODE
S1=3 ON
S1=3 ON
AUX. IN
AUX. IN
+ - + -
TROUBLE
CKT.
-
OUTPUT CKT.
OUTPUT CKT.
-
+
+
AUX./AUDIO MODE
AUX./AUDIO MODE
AUXILIARY
MODE
P1=2&3
S1=1&2 ON
S1=1&2 ON
PC LINE
PC LINE
A B A B
DEVICE
ALL OTHERS - POWER LIMITED
ALL OTHERS - POWER LIMITED
CAT. NO. 70-200200-001
CAT. NO. 70-200200-001
ASHLAND, MA 01721 U.S.A.
ASHLAND, MA 01721 U.S.A.
KIDDE-FENWAL, INC.
KIDDE-FENWAL, INC.
FM
APPROVED
R
L
U
TM
Figure K-1. ASM Front Panel
K-2
ADDRESSING AND REGISTRATION
As with any SmartOne loop device, addressing is through the
Kidde hand-held programmer (P/N 74-200013-001) or the PEGA-
sys control panel menu/keypad as described in Chapter 2 of this
manual.
Module-programmable parameters include owner’s-location mes-
sage, non-silenceable (waterflow), walk test, drill mode and si-
lence. The programming process is described in PEGAsys™
Configuration Software (PCS) Program User’s Guide, 76-014, (P/
N 06-235766-001).
Addressing and programming the module's registration into the
PEGAsys system is described in Paragraph 2-8 (and sub-para-
graphs) of this manual. Registration of the module at the PEGA-
sys panel is mandatory to ensure proper operation.
K-3
OPERATION
Once installed and configured, the ASM requires little or no main-
tenance. The module's 24 VDC or 25/70 VAC modes can be
changed from the factory defaults using switch S1 and jumper P1
(See Figure K-1).
K-4
FUNCTIONAL DESCRIPTION
The SmartOne™ Addressable Signal/Sounder Module (ASM) pro-
vides a fully supervised remote-output circuit for connection to
either 24 VDC audible/visual notification signaling devices or 25/
70.7 V RMS speakers. The module provides continuous internal
supervision of:
•
Alarm contact position
•
Connections to loop voltage and communications
•
Internal power supply
•
Auxiliary power supply connections and status
•
Memory status
The output circuit is monitored by reverse polarity and will not
actuate into a short. If the circuit has a ground fault, open, short or
a relay contact failure, the device will transmit a specific trouble
status.
A status LED is mounted on the unit and indicates the output cir-
cuit status by a 2 second (active) or 9 second (normal) flash in-
terval. A trouble condition inhibits the status LED completely.
K-5
MAINTENANCE OR REPLACEMENT
The ASM is shipped from the factory as an assembled compo-
nent and is not field serviceable. Little or no maintenance is re-
quired.
Testing is accomplished through the testing capabilities of the
PEGAsys panel. See Chapter 5, Troubleshooting and Corrective
Maintenance, for particulars. In the event of a failure, the module
should be replaced.
For replacement, follow the instructions in the ASM Installation
Data Sheet.