P/N 06-237058-001
1-25
February 2012
1-15
SIGNALING LINE CIRCUIT (SLC) DEVICES AND MODULES
1-15.1
SmartOne
®
Devices
The ARIES NET
Link
supports the SmartOne Series of intelligent smoke and heat detectors. These
detectors have their own data transceivers, micro-controllers, micro-controller memory, and
algorithms that allow the detectors to determine whether a normal, pre-alarm, alarm, or trouble
condition exists at their monitoring locations.
Table 1-4. Supported SmartOne Intelligent Devices
Device
Description
Illustration
SmartOne Ionization
Smoke Detector,
Model CPD-7052
A low-profile, intelligent smoke detector that uses
an ionization sensing chamber. This detector can
be utilized for open-area coverage or can be
mounted in a duct with air velocities up to 2,000
feet per minute.
SmartOne
Photoelectric Smoke
Detector,
Model PSD-7152
A low-profile, intelligent smoke detector that uses a
light-scattering sensing chamber. This detector can
be utilized for open-area coverage or can be
mounted in a duct with air velocities up to 4,000 feet
per minute.
SmartOne Thermal
Detector,
Model THD-7252
The Model THD-7252 Thermal Detector is a low-
profile, intelligent heat detector that uses a
thermistor sensing chamber for fast response. This
detector can be used for open-area coverage on low
(< 10 ft.), flat ceilings with a spacing up to 70 ft.
Flanged Detector
Base, Model 6SB
The Model 6SB Detector Base is used in
applications where the detector's installed
appearance is a primary consideration. This base
mounts to standard 3-, 3½-, and 4-inch electrical
boxes.
Flangeless Detector
Base, Model 4SB
The Model 4SB Detector Base is used in underfloor
applications, or in applications where the detector’s
installed appearance is not a primary
consideration. This base mounts to standard 3- or
3½-inch electrical boxes.
Detector Base Adapter,
Model MA-002
The Model MA-002 Detector Base Adapter allows
the low-profile SmartOne detectors to be retrofitted
into the older-style SmartOne detector base, P/N
70-400000-001.
Duct Housing,
Model DH-2000
The Model DH-2000 Duct Housing is used to
enclose an intelligent smoke detector that is
monitoring for smoke in an air duct but located
outside of the duct. The duct housing is used with
inlet and outlet tubes that allow the air in the duct
to be sampled uniformly and transported to the
enclosed smoke detector for obscuration-level
measurement.
DUCT
DETECTOR
MODEL
DH-2000
R
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......