Component Descriptions
06-237518-001
2-17
July 2018
2-5.1
Back-Plate Manifold
Use the back-plate manifold in systems using selector valves to provide pressure to the needed
selector valve. The back-plate manifold provides a pressure reduction valve so that manifold
pressure can be used to operate selector valve. The backplate manifold includes solenoids to
control which selector valve will receive pressure.
Note:
The solenoid on the back-plate manifold leading to the hazard being protected by the
discharge must be continuously powered during the system discharge.
Figure 2-22. 3 Area Back-Plate Manifold
2-5.1.1
Back-Plate Manifold Hose
Use the hose (P/N 01-3273-1200) to connect the back-plate manifold to the selector valves.
Figure 2-23. Back-Plate Manifold Hose
Table 2-17. Kidde Fire Protection IGS Back-Plate Manifold Part Numbers
Part Number
Description
01-3508-0002
Back-Plate Manifold - 2 Area, Selector/Divertor Valve Control, 8 Bar
01-3508-0003
Back-Plate Manifold - 3 Area, Selector/Divertor Valve Control, 8 Bar
01-3508-0004
Back-Plate Manifold - 4 Area, Selector/Divertor Valve Control, 8 Bar
01-3508-0005
Back-Plate Manifold - 5 Area, Selector/Divertor Valve Control, 8 Bar
Table 2-18. Kidde Fire Protection IGS Selector Valve Part Numbers
Part Number
Description
01-3273-1200
Back-Plate Manifold Hose
-Kerr
Back-Plate Manifold Hose
(P/N 01-3273-1200)
Summary of Contents for 400 Series
Page 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Page 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Page 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 189: ......