FZ-USV-230 (SXM 2540)
[ENG]
Stand: 10.03.2008
page 21 from 21
6. Recommended Maintenance
It is recommended that the unit should be tested from the first “power up”, at least
once a year to verify continued correct operation. Please check all functions for correct
safety monitoring. Please check also the function of the Genius / Fliethomatic under
normal conditions and with different simulated errors for example, mains power (AC)
failure, battery disconnected.
Testing should also be in accordance with the following recommendations ;
Output Voltage Test
Voltage output should be tested under normal load conditions to verify correct levels.
Test the voltage when the Genius / Fliethomatic operates to lock or unlock the door.
Battery Test
Battery should be checked for full charge under normal load conditions. This test
should verify correct voltage at
a) battery terminals, and
b) battery output position on the circuit board to ensure the integrity of all inter-
connecting wiring.
It is recommended to replace the battery at least every 4 years.
Please give used batteries to the recycling, service company.
7. Battery Stand-By Mode Specifications
Standby
100
lock / unlock
200
lock / unlock
500
lock / unlock
Non-stop
operation
1 Genius
40 Hr
35 Hr
28 Hr
12 Hr
4 Hr
2 Genius
20 Hr
17 Hr
14 Hr
6 Hr
2 Hr
3 Genius
13 Hr
11 Hr
9 Hr
4 Hr
1,3 Hr
4 Genius
10 Hr
8 Hr
7 Hr
3 Hr
0,5 Hr
1 Genius with coupling relay
29 Hr
24 Hr
20 Hr
7 Hr
3 Hr
All data is approximate in the 24 VDC version with two 12 Volt batteries connected in
series, fully charged with a battery capacity of 7Ah.