![Keysight Technologies N6900 Series Operating And Service Manual Download Page 151](http://html1.mh-extra.com/html/keysight-technologies/n6900-series/n6900-series_operating-and-service-manual_1962217151.webp)
Programming the Digital Port
Fault/Inhibit System Protection
Digital Control Port
A Digital Control Port consisting of seven I/O pins is provided to access various control functions. Each
pin is user-configurable. The following control functions are available for the I/O pins. See
for details on the SCPI commands to program the Digital Port.
The following table describes the possible pin configuration for the digital port functions. For a
complete description of the electrical characteristics of the digital control port, refer to the
section.
Function
Description
DIO
General-purpose ground-referenced digital input/output function. The output can
be set with [SOURce:]DIGital:OUTPut:DATA.
DINPut
Digital input-only mode. The digital output data of the pin is ignored.
EXPRession<1-8>
A user-defined expression drives the pin.
FAULt
Applies only to pin 1. Pin 1 functions as an isolated fault output. The fault signal is
true when any output is in a protected state. Pin 2 serves as the isolated common
for pin 1. When pin 1 is set to the FAULt function, the instrument ignores any
commands to program pin 2. Queries of pin 2 will return FAULt. If pin 1 is
changed from FAULt to another function, pin 2 is set to DINPut.
INHibit
Applies only to pin 3. When pin 3 is configured as an inhibit input; a true signal at
the pin will disable the output.
ONCouple
Applies only to pins 4-7. The ONCouple pin synchronizes the output On state
between instruments. Only one pin can be configured as an ONCouple. The pin
functions as both an input and an output.
OFFCouple
Applies only to pins 4-7. The OFFCouple pin synchronizes the output Off state
between instruments. Only one pin can be configured as an OFFCouple. The pin
functions as both an input and an output.
Keysight N6900/N7900 Series Operating and Service Guide
151
4 Using the Advanced Power System
Summary of Contents for N6900 Series
Page 1: ...Keysight Advanced Power System N6900 N7900 Series Operating and Service Guide...
Page 2: ......
Page 63: ...1 kW Models Keysight N6900 N7900 Series Operating and Service Guide 63 1 Quick Reference...
Page 64: ...2 kW Models 1 Quick Reference 64 Keysight N6900 N7900 Series Operating and Service Guide...
Page 78: ...2 Installing the Instrument 78 Keysight N6900 N7900 Series Operating and Service Guide...