OPERATION MANUAL

RK-2006LPP

AUGER FITTED SOLID FUEL

BOILER TEMPERATURE CONTROLLER

Version DC19

Summary of Contents for RK-2006LPP

Page 1: ...OPERATION MANUAL RK 2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER Version DC19...

Page 2: ......

Page 3: ...electrical connection diagram For connection of stoker alarm indicator and ash removal system the additional module UM 1 shall be applied CAUTION Before plugging in the controller first check if the...

Page 4: ...ere is 1 Display 2 Fan indicator 3 Auger indicator 4 Ignition glow plug indicator 5 Central heating circuit pump indicator 6 Hot tap water pump or mixing pump indicator 7 Room thermostat operation and...

Page 5: ...peration mode Description STOP Boiler control stopped Controller maintains central heating and domestic water pump operation but automatic ignition does not follow STAND BY Controller maintains centra...

Page 6: ...the technician IGNITION mode follows till flame is detected If the flame is not detected within the specified time the controller activates Out of fuel alarm Pressing STOP button exceeding time limit...

Page 7: ...n to ensure complete fuel combustion and the burner cool down Fan power when in EXTINCTION SHUT DOWN mode is determined by the technician When EXTINCTION SHUT DOWN is finished the controller is switch...

Page 8: ...O F F U E L Emergency alarm Depending on construction type the boiler may be equipped with emergency sensor e g hopper cover sensor Activation of the alarm will result in fan and auger turning off and...

Page 9: ...ler water temperature set point is equal to the programmed Boiler max temperature service setting the controller will engage central heating pump If water boiler temperature increases above 93 C it wi...

Page 10: ...d the controller activates alarm A L A RM R E T U R N T E M P S E N S O R CAUTION This alarm does not require cancellation The alarm is deactivated automatically if repairs are made 4 Review of user s...

Page 11: ...work time Burner start up counter 4 1 Fuel type selection RK 2006LPP controller enables programming ignition settings for four different fuel types Fuel type parameter enables switching between partic...

Page 12: ...n follow at the same time H O T W A T E R P R I O R I T Y N O Bacterial flora liquidation in domestic water tank the controller enables manual activation of program for bacterial flora liquidation in...

Page 13: ...ion of the temperature detector of burner fuel ignition If the system is fitted with optical fire burner detector parameters change and viewing is unavailable Burner measured temperature this paramete...

Page 14: ...setting Table 3 Service settings Light Parameter Min Max No Language selection See description Fan Fan modulation during boiler start NO YES Min fan speed during heating up 1 100 Max fan speed during...

Page 15: ...nsion time 1min 10min Mixing pump engaging temperature 30 C 60 C Mixing pump work hysteresis 1 C 9 C Thermostat Boiler minimum temperature 30 C 200 C Boiler maximum temperature 200 C 400 C Boiler uppe...

Page 16: ...increase fan speed up to the selected Max fan speed during boiler start setting I G N I T I O N M O D U L S T A R T D E L A Y 5 0 s Fan speed during ignition this parameter describes power of the fan...

Page 17: ...venge This setting is unavailable if Fan scavenge air purging setting was not selected F A N S C A V E N G E P A U S E T I M E 1 m i n Fan speed during scavenge air purging this parameter specifies fa...

Page 18: ...programmed setting specifies feeding time in percent in relation to the time of whole work cycle F U E L D O S E F O R M A X P O W E R 5 0 Fuel feed for min burner power this parameter specifies fuel...

Page 19: ...hed off S T O K E R E M P T Y I N G T I M E 4 0 s Auger ignition test this parameter provides functionalities of X emergency input If NO setting was selected then X input will be used for connection o...

Page 20: ...lame of the light equals zero F D 1 C O R R E C T I O N 0 Hysteresis loss of flame depending on the type of flame detector this parameter specifies how many degrees or units in relation to the thresho...

Page 21: ...ng mechanism In this case the output DATA is working as an external alarm CYCL means the mode in which the cleaning procedure is run after the firing and repeated at regular intervals until burner shu...

Page 22: ...ies the minimum number of hours the burner must in order to start cleaning If the minimum time is not reached the cleaning will not run even if there was a required number of shut downs Setting the pa...

Page 23: ...y heating system is provided with domestic water tank and charge pump this circuit may be switched off or used for control of the pump that mixes the return water in the boiler Domestic water path if...

Page 24: ...ng is available if domestic water path EXISTS setting was selected H W P U M P W O R K E X T E N S I O N Y E S Domestic water pump extension time this parameter specifies the time lapse when domestic...

Page 25: ...t burner extinction shut down B O I L E R U P P E R H Y S T E R E S I S 5 c Burner power switching hysteresis when the programmed boiler water temperature is obtained the controller is switched to min...

Page 26: ...of the entry of the room thermostat to the operation of the controller NORMAL in this mode the thermostat contacts are closed when the controller starts firing up the burner and the boiler strives to...

Page 27: ...ervice parameters for current fuel type only 5 10 Output testing It is possible to test particular preset functions This is available only if the controller is in STOP mode before switching to service...

Page 28: ...ta Power Supply 230V 10 50Hz Power consumption without fan and pump 4VA Burner temperature measurement range KTY 81 210 9 109 C 1 C Temperature measurement range KTY 81 210 9 109 C 1 C Burner temperat...

Page 29: ...10 Notes Light Parameter Settings 1 2 3 4 Thermostat Boiler max power HTW pump Domestic water desired temperature Domestic water heating priority Igniter Brightness when fuel ignition has occurred FD...

Page 30: ...Fan scavenge air purging Fan scavenge air purging blow time Fan scavenge air purging pause time Fan speed during scavenge Auger Auger filling time Initial fuel feed Fuel feed cycle Fuel feed during i...

Page 31: ...time without cleaning CH pump Central heating pump work mode Central heating pump periodic work Central heating pump periodic work time HTW pump Domestic water path Domestic water heating hysteresis B...

Page 32: ...32...

Page 33: ...33...

Page 34: ...34...

Page 35: ...000 4 11 2005 U PN EN 60730 1 2002 A1 2006 U A12 2004 A13 2005 PN EN 60730 1 2005 A14 2006 PN EN 60730 2 9 2006 PN EN 61000 3 2 2006 U PN EN 61000 3 3 1997 A1 2005 A2 2006 IS1 2006 Information on disp...

Page 36: ...Manufacturer Przedsi biorstwo Wielobran owe KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...