OPERATION MANUAL
RK-2006LPG
Pellet fuel burner fitted boiler temperature controller.
Version 6A25
Page 1: ...OPERATION MANUAL RK 2006LPG Pellet fuel burner fitted boiler temperature controller Version 6A25...
Page 2: ...on burner work 15 Alarms cancellation 15 Setting the parameters service mode 15 Table 3 Table service parameter 16 Language selection 18 Brightness saturation contrast of the display 18 Service settin...
Page 3: ...locations that shall be dry Figure presents the electrical connection diagram For connection of stoker alarm indicator and ash removal system the additional module UM 1 shall be applied CAUTION Befor...
Page 4: ...et the preset boiler temperature In this hands U need to turn the boiler thermostat knob 4 to set the correct value and confirm it with the OK button or press the knob CAUTION If you enter the room th...
Page 5: ...5 Boiler water temperature 6 Feeder work indicator 7 CH pump work indicator 8 Burner capacity indicator the higher the capacity the brighter the flame 9 Cleaning device work indicator 10 Blower 11 Sto...
Page 6: ...tains central heating and domestic water pumps operation only to protect the boiler against overheating and auger channel ignition Room thermostat contacts closing call for heat and domestic water tem...
Page 7: ...ER OPERATION MODE Depending on desired parameters the controller may gradually reduce fuel and air rate feeding to reduce burner power as much as boiler water temperature corresponds to the programmed...
Page 8: ...e auger manual refilling function When device is in STOP mode press START and hold button for 5 seconds to start refilling Refilling follows according to the time programmed by the technician or until...
Page 9: ...the technician Out of fuel alarm will be activated To turn on the controller again first refill fuel cancel the alarm with STOP button and begin setting up process by pressing START button Emergency a...
Page 10: ...troller its damage will result in activation of the alarm and switching into STAND BY mode Protection against overheating and overheating of the boiler RK 2006LPG is protected against overheating of t...
Page 11: ...the controller turns off the domestic water pump and activates alarm CAUTION This alarm does not require cancellation The alarm is deactivated automatically if repairs are made Return water temperatur...
Page 12: ...perature 30 C 60 C 1 6 Domestic water heating priority NO YES 1 7 Domestic water tank bacterial flora liquidation program NO YES 1 8 Measured domestic water temperature 1 9 Measured return water tempe...
Page 13: ...heating priority this parameter specifies operation of central heating and domestic water pumps during hot water preheating When priority is selected during operation and hot water preheating the con...
Page 14: ...ing pump and return temperature sensor this option enables view of the return water temperature Otherwise this option in unavailable Flame optical detection parameters These parameters specify operati...
Page 15: ...our of the device at maximum or minimum power 1 16 Burner start up counter Reading of this counter defines start number of the ignition attempts 1 17 Boiler on the parameter informs the user if the bo...
Page 16: ...the device A list of all service parameters presented in the table Table 3 Table service parameter Lp Parameter Min Max 2 x Overall 2 1 Language see description 2 2 Brightness of the display 2 3Satur...
Page 17: ...Duration of the CH pump cyclic work 1min 99min 7 3 Interval duration in the CH pump operation 1min 99min 8 x HTW pump 8 1 Domestic water path OFF ON MIXING PUMP 8 2 Domestic water heating hysteresis...
Page 18: ...oller it is possible to test various output devices This feature is available in service mode only if the adjustment process is stopped ie The regulator before entering the service mode was in STOP mo...
Page 19: ...with speed according to the selected Min fan speed during boiler start setting After time expire the controller will increase fan speed up to the selected Max fan speed during boiler start setting 3...
Page 20: ...tching on of the fan during burner operation for the purpose of removal of accumulated gases 3 11 Fan scavenge air purging blow time this parameter specifies blow time This setting is unavailable if F...
Page 21: ...auger operation cycle includes fuel feeding and feeding pause This parameter specifies the time of the whole cycle The desired value specifies all burner work modes which require fuel feeding ignition...
Page 22: ...tion to the time of whole work cycle 4 7 Stoker work mode This parameter defines the operation of the internal tray stoker OFF the burner without the stoker CYCL stoker is switched on periodically reg...
Page 23: ...uring extinguishing of feeder feeding initial fuel dose portion and during burner shut down This setting is unavailable if the stoker is switched off 4 12 Auger ignition test this parameter provides f...
Page 24: ...2 sensor In case of higher temperatures PT 1000 sensor shall be used For flame brightness measurement FD 1 optical detector shall be used 5 2 Indication correction of flame optical detector only when...
Page 25: ...of the burner If flame is not detected within the time programmed in this parameter the controller will repeat ignition cycle 5 7 Ignition try count this parameter specifies how many times ignition m...
Page 26: ...ogrammed in this setting This function ensures combustion of all fuel remains and burner cool down 6 x Cleaning mechanism 6 1 Furnace cleaning mode this parameter specifies the way the cleaning mechan...
Page 27: ...ally cleaning involving extinguished hearth start cleaning mechanism at the time set in the parameter TIME OPENING THE MECHANISM and run the fan with the power specified in the parameter SPEED FAN THE...
Page 28: ...UTO mode or COMBI and determines which in turn goes off to start the procedure of cleaning 6 8 Minimum operating time without cleaning this parameter is available only when the cleaning mechanism oper...
Page 29: ...he option of turning the CH pump occasionally to mix the water in the heating circuit The pump is turned on for the duration defined in the parameter TIME DURATION of CH PUMP WORK The option is availa...
Page 30: ...s available if domestic water path EXISTS setting was selected 8 3 Increase temperature during domestic water heating Closing thermostat contacts means that boiler operation will follow according to t...
Page 31: ...ion In this case after working for the hot water boiler water temperature may be higher than the temperature required to heat the rooms This may result in extinction of the burner due to exceeding the...
Page 32: ...ler that can be programmed with thermostat s knob 9 2 Maximum boiler temperature this parameter specifies boiler max programmed temperature setting which can be programmed with thermostat s knob It is...
Page 33: ...r water temperature corresponding to the programmed setting 9 8 Burner power modulation factor this parameter specifies degree setting when the controller will reduce burner power before boiler water...
Page 34: ...case the boiler will operate continuously maintaining the set temperature of the boiler thermostat knob 9 10 The time constant of adaptation this parameter is available when the ther mostat is workin...
Page 35: ...ol 10 2 MODBUS device number 1 247 allows the user to determine the number of the device attributed to your controller and to avoid errors when a number of devices are switched to the bus Default valu...
Page 36: ...ERVICE changing all of the parameters is possible 10 6 Terminal access level defines to what extent access can be obtained through the remote terminal NO no access through the remote terminal READ OUT...
Page 37: ...wer Supply 230 V 10 50 Hz Power consumption without fan and pump 4 VA Burner temperature measurement range KTY 81 210 9 109 C 1 C Temperature measurement range KTY 81 210 9 109 C 1 C Burner temperatur...
Page 38: ...38...
Page 39: ...PN EN 61000 3 3 2011 EN 55022 2010 PN EN 55022 2011 Information on disposal This appliance is marked according to the European Directive 2002 96 EC on Waste Electrical and Electronic Equipment WEEE Th...
Page 40: ...Manufacturer Przedsi biorstwo Wielobran owe KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...