NC-485X Network Converter

Application Note

Page 1 of 13

P/N: 01967-001 Rev. C

1.0

Purpose of this Document

This document discusses how to setup, configure, and use the LAN-520X LAN

1

 and NC-485 

Network Converter to provide LAN/WAN Ethernet connectivity between a PXL-500/PXL-510 
Master controller and one or more PXL Slave controllers.

This document discusses how to setup, configure, and use the LAN-520X with the NC-485X 
Network Converter to provide LAN/WAN Ethernet connectivity between two or more PXL RS-485 
network segments. The following topics are covered:

Overview

LAN-520X with NC-485X Network Converter Setup

Using the LAN-520X with Multiple PXL Networks

Basic Ethernet Troubleshooting

NOTE: The NC-485X is an updated version of Keri’s NC-485 device. If you are using the new NC-
485X with a LAN-520, you must use the updated LAN-520X module. The original NC-485 
Network Converter is NOT compatible with the new LAN-520X.

2.0

Overview

The LAN-520X, when used in conjunction with a NC-485X, provides companies the ability to use 
their existing LAN/WAN for RS-485 communication between a Master PXL and multiple Slave 
PXLs. Since LAN/WAN networks can be global, using the LAN-520X with a NC-485X provides the 
ability to have Slave PXLs located throughout the world managed from one central location.

NOTE: If all network segments are not located within the same time zone, the time zone where the 
Doors software is located will be used. For example, a site has network segments located in both 
the Mountain and Pacific time zones with the Doors software on a computer in the Pacific time 
zone. If an Auto Unlock/Lock is set on a controller in the Mountain time zone for 9 am, the 
controller will not auto unlock/lock until 9 am Pacific time (the location of the Doors software), 
which would then be 10 am Mountain.

The LAN-520X supports two communication channels. Channel 1 is used for RS-232 communication 
and Channel 2 is used for RS-485 communication. The RS-232 communication is identical to that of 
a LAN-505. The LAN-520X replaces the LAN-505 for serial over Ethernet communication. In order 
to provide RS-485 communication over Ethernet, the LAN-520X must be connected to the NC-485X 
Network Converter.

The drawing below shows a conceptual PXL network. Each PXL network segment contains one 
LAN-520X connected to a NC-485X. The network segment containing the master must have the 
LAN-520X/NC-485X connected to the PXL Master. Only one LAN-520X/NC-485X combo can be 

1. The LAN-520X may be used with a PXL-500/PXL-510 only.

Summary of Contents for NC-485X

Page 1: ...al using the LAN 520X with a NC 485X provides the ability to have Slave PXLs located throughout the world managed from one central location NOTE If all network segments are not located within the same...

Page 2: ...twork segments can be connected to a PXL Master It is also possible to connect a PXL network outside of the Local LAN by utilizing a VPN or WAN Figure 1 Single Site with Multiple Network Segments 3 0...

Page 3: ...be configured in Master mode Only one LAN 520X Master can exist in a PXL network All other LAN 520X units within a PXL network must be configured in Slave mode This document assumes that Channel 1 of...

Page 4: ...e two ways to open Telnet through the Lantronix DeviceInstaller window or by opening a DOS box From the DeviceInstaller page locate and double click on the IP address of the LAN 520X Select the Telnet...

Page 5: ...isplayed This value must be 10002 for proper communication between Doors and the LAN 520X If this value is not 10002 type 10002 to overwrite the original value NOTE This value should not be changed un...

Page 6: ...nd Port number for each slave unit The Port number should be set to 10002 11 Once all the IP addresses and Port numbers have been entered enter an IP address of 0 0 0 0 to exit and press N when the Ch...

Page 7: ...ress Enter simply click the box again to establish a connection to Telnet 2 Once Telnet connects with the LAN 520X all current configuration information is displayed and the cursor is placed at the Yo...

Page 8: ...are on the same LAN Subnet see Using Multiple PXL Networks on the Same LAN Subnet on page 9 or instructed to do so by either Keri Systems or Lantronix Technical Support Staff 9 Press Enter until the C...

Page 9: ...ort number For each PXL Network change the Channel 2 Port setting on the LAN 520X Master and Slaves to a unique number It is recommended that the port number be incremented by one digit for each netwo...

Page 10: ...ion Settings on page 4 4 2 Verify the LAN 520X is Online 1 Ping the IP address of the LAN 520X If the ping fails that means a communication connection cannot be made Possible reasons are There is no p...

Page 11: ...X LAN connection is the problem then only that LAN 520X will have LEDs 1 2 and 4 solid NC 485X Cable Connected LED 1 2 4 Solid LED 2 Blinking LED 1 4 Solid LED 2 Blinking NC 485X Cable Not Connected P...

Page 12: ...ork Administrator Enter the Gateway IP Address in the Server Properties of the LAN 520X may be Master or Slave Master PXL is unable to communicate to any Slave PXL J103 lead on the Master s NC 485X re...

Page 13: ...System s installation of the Device Installer has a modified version of the Lantronix device list Update the list by modifying the ProductInfobase txt file in the Lantronix DeviceInstaller folder to...