background image

2

228-1671 REV 2

 110122

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102



http://www.kepcopower.com   



 email: [email protected]

Figure 3 shows HSF’s in slots 3 and 4 connected in paral-
lel with forced current sharing and a close-on-fail alarm
circuit. Both HSF modules are configured for output volt-
age to be adjusted from the front panel trimpot (factory
default setting). See 

Operator Manual

 for other output

voltage adjustment options.

Configure DIP 4:

1. Set positions 1 and 2, to OFF to disable local sensing

for slot 4. 

2. Set positions 3 and 4, to ON. This connects sense lines

(+S to +S and –S to –S) for slots 4 and 3.

3. Set position 5, to ON. This connects the current share

bus (CB) for slots 4 and 3.

4. Set positions 6 and 7 to ON. Position 6 connects the

normally open ALARM (N.O.) lines and position 7 con-
nects the ALARM (COM) (common) for slots 4 and 3,
implementing a close-on-fail alarm circuit (see equiva-
lent schematic shown in Figure 3. If either PS3 or PS4
fails, a contact closure provides continuity across pins 7
and 14 of both I/O 4 and I/O 3.

5. Set position 8 to OFF. This position is only set to ON for

open-on-fail alarm circuits.

6. Set position 9 to OFF. Isolates RV (remote voltage)

lines between slot 4 and 3, however RV is not used
(output voltage is controlled by the front panel trimpot).

7. Set position 10 to ON. This connects the common lines

(-COM) for slots 4 and 3.

TABLE 1.  REAR PANEL DIP SWITCH FUNCTIONS

DIP 

SWITCH 

POSITION

FUNCTION

DIP SWITCH SETTINGS

1, 2

Local /

Remote 

Sensing 

Selection

Position 1 connects V+ to S+, Position 2 connects V– to S– . 
Both required ON (factory default) for independent operation with Local Sensing. and for the first slot of a parallel config-
uration.
Both required OFF for: 

a) Independent configurations using Remote Sensing.
b) All series connections.
c) All parallel configurations (except for the first slot); use switch positions 3, 4 set to ON to parallel sense connections 
from the first slot.

3, 4

Connect

Sense

+ and –

in parallel

Position 3 coS to adjacent slot +S, Position 4 connects –S to adjacent slot –S.
Both required OFF (factory default) for all configurations except parallel configurations using DIP switch settings to con-
nect the sense leads in parallel.
Both required ON for parallel configurations using DIP switch settings to connect the sense leads in parallel. 

5

Current 

Balance

(forced 
current 

share)

Required ON for parallel operation with forced current share (connects current share lines in parallel) unless connec-
tions are made via external wires
Required OFF (factory default) for independent and series configurations.

6, 7

Close on 

Failure 

Alarm

When set to OFF (factory default), individual power supplies produce closure between I/O connector N.O. and COM 
pins upon failure .
When set to ON, parallels N.O pins of adjacent slots to allow a single alarm to provide failure indication (contact closure 
between N.O. pin and COM pin) if any one of many power supplies fails.

8

Open on 

Failure 

Alarm

When set to OFF (factory default), individual power supplies produce open between I/O connector N.C. and COM pins 
upon failure.
When set to ON, connects N.C to COM between adjacent slots so that individual alarms are connected in series. This 
allows a single alarm to provide failure indication (contact open between N.C. pin and COM pin) if any one of many 
power supplies fails.

9

Remote 

Voltage

When both set to OFF (factory default), allows independent voltage control of each power supply
When both set to ON, enables control of multiple supplies from one power supply designated as the Master. 
Required OFF (factory default) for independent and series configurations. 

10

-Common

Reviews: