background image

MST-MHT SERIES 071320

2-11

FIGURE 2-5.    OUTPUT IMPEDANCE VS. FREQUENCY

A practical model for a voltage-stabilized Power Module includes a series inductance represent-
ing d-c and low frequency source impedance. Load leads should have minimum voltage drops
(error sensing discussed in PAR. 2.10 below) and minimum inductance (error sensing does not
compensate for this). Similarly a model for a current stabilized Power Module includes a parallel
capacitor representing the d-c and low frequency source impedance. These considerations are
important if:

The load is constantly changing value.

The load is switched “on” and “off.” 

The output of the Power Module is step programmed.

The load is reactive.

Dynamic output response of the Power Module is of concern.

2.9

CONNECTION, GENERAL

All input and output connections between the Power Module and RA 55H Rack Adapter are
made automatically when the Power Module is fully seated in a Rack Adapter slot. Refer to the
Rack Adapter Instruction Manual for instructions on connecting RA 55H output connectors to
the load, a-c input power, and control signals.

The d-c output connector, labeled DC OUTPUT, is located on the back of chassis (Figure 2-6).
Adapter Kit 219-0618 is must be installed on the DC Output Connector at the rear of the chassis
to meet the all specifications listed in Table 1-1. For the DC Output Connector pin designations
on MST-MHT units via Adapter Kit 219-0618 refer to Table 2-5 and Figure 2-6.

Summary of Contents for MST 100-2MHT

Page 1: ...revision for your par ticular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco I...

Page 2: ......

Page 3: ...ired equipment rack utilizing a three wire grounded mains connection See wiring section of this manual for complete electrical wiring instructions EN61010 1 2001 Cl 6 10 1 4 This power supply has seco...

Page 4: ...performing any servicing This product is designed for use with nominal a c mains voltages indicated on the rating nameplate The PROTECTIVE EARTHING CONDUCTOR TERMINAL must be properly con nected prio...

Page 5: ...ounding 2 6 2 6 2 D C Output Grounding 2 6 2 7 Preliminary Check out 2 7 2 7 1 Required Equipment 2 7 2 7 2 Initial Setup 2 7 2 7 3 Checkout Procedure 2 9 2 8 Power Module to Load Interface 2 10 2 9 C...

Page 6: ...ode Protection 3 7 3 9 Calibration 3 8 3 9 1 Equipment Required 3 8 3 9 2 5 Volts Reference Adjust R49 3 10 3 9 3 Output Voltage EO Zero Adjust R11 3 10 3 9 4 Current Sense Zero Adjust R50 3 10 3 9 5...

Page 7: ...iguration for Preliminary Checkout 2 9 2 5 Output Impedance vs Frequency 2 11 2 6 Connector Locations and Pin Assignments 2 13 3 1 Calibration Test Set up 3 10 1 1 MST MHT Model Parameters 1 2 1 2 MST...

Page 8: ...iv MST SERIES 071320 FIGURE 1 1 MST POWER SUPPLY...

Page 9: ...nts current share hot swap built in polarity reversal constant current mode and greater power 180W to 200W MST MHT power modules employ a switch mode preregulator for high efficiency and power density...

Page 10: ...x TABLE 1 2 MST MHT GENERAL SPECIFICATIONS SPECIFICATIONS RATING DESCRIPTION CONDITION INPUT A C Voltage nominal 100 250V a c Single phase range 90 264 Va c Brownout Voltage 85Vrms Frequency nominal 5...

Page 11: ...condition Isolation Output Case 500 V d c Display Voltage 3 5 Digit LED red Front panel For reference only Current 3 5 Digit LED red Status Indicators Voltage Mode Green LED Current Mode Amber LED Cur...

Page 12: ...ilent HP 66000 Series PHYSICAL Type of Construction Enclosed plug in style includes status LEDs two digital meters handle and ON OFF switch Cooling Internal D C Cooling Fans Exhaust to rear Module Dim...

Page 13: ...MST MHT SERIES 071320 1 5 FIGURE 1 1 MST MHT POWER SUPPLY MECHANICAL OUTLINE DRAWING...

Page 14: ...isabling the MST MHT as a current source means shorting the power supply s output terminals Polarity reversal relays are installed but not supported at this time If polarity reversal is needed refer t...

Page 15: ...Adapter Additional accessories are listed in Table 1 3 TABLE 1 3 ACCESSORIES ACCESSORY PART NUMBER USE OUTPUT LOAD CONNECTOR ADAPTER supplied with RA 55H Rack Adapter KIT 219 0618 Allows output load c...

Page 16: ......

Page 17: ...lt age and frequency ranges without adjustment or modification 2 4 COOLING The power transistors and rectifiers in the MST MHT Power Module are maintained within their operating temperature range by m...

Page 18: ...rce see PAR 3 2 1 CURRENT MODE indicator amber LED Goes on to indicate MST MHT is operating as a current source see PAR 3 2 2 POLARITY REVERSED indicator green LED Goes on when negative output program...

Page 19: ...h the top of the unit see Figure 2 2 and can be changed in accordance with Table 2 4 This address is set at Kepco to 1 NOTES 1 Although 31 unique addresses are provided the maximum number of instrumen...

Page 20: ...1 0 0 13 0 1 1 0 1 14 0 1 1 1 0 15 0 1 1 1 1 16 1 0 0 0 0 17 1 0 0 0 1 18 1 0 0 1 0 19 1 0 0 1 1 20 1 0 1 0 0 21 1 0 1 0 1 22 1 0 1 1 0 23 1 0 1 1 1 24 1 1 0 0 0 25 1 1 0 0 1 26 1 1 0 1 0 27 1 1 0 1...

Page 21: ...in use refer to PAR 2 5 1 to change the address setting NOTE If the Power Module is already installed in a Rack Adapter and it is necessary to change the control bus address the Power Module must firs...

Page 22: ...formance considerations and safety requirements For optimum performance certain rules must be observed These rules are described in detail in the following paragraphs 2 6 1 SAFETY GROUNDING National a...

Page 23: ...circuit and returned to ground with a single wire This method is dependent on the specific application 2 7 PRELIMINARY CHECK OUT 2 7 1 REQUIRED EQUIPMENT Host computer w communication cable for select...

Page 24: ...d i e a c power applied to the Controller first and MST MHT power modules last the operator must send an IEEE 488 Device Clear command via the Host Computer prior to issuing other commands For proper...

Page 25: ...mands from the host computer to set the MST MHT Power Module to Voltage Mode program output voltage to EMAX current limit to IMAX and enable the output e g for MST 36 5MHT issue the following commands...

Page 26: ...current MEAS CURR Verify that read back current is IMAX e g 5A for MST 36 5MHT 2 8 POWER MODULE TO LOAD INTERFACE The general function of a voltage or current stabilized Power Module is to deliver rat...

Page 27: ...put of the Power Module is step programmed The load is reactive Dynamic output response of the Power Module is of concern 2 9 CONNECTION GENERAL All input and output connections between the Power Modu...

Page 28: ...terminals directly to the load will compensate for voltage drops in the load interconnection scheme up to 0 5V maximum per wire the termination point of the error sensing leads should be at or as clo...

Page 29: ...071320 2 13 2 14 Blank FIGURE 2 6 CONNECTOR LOCATIONS AND PIN ASSIGNMENTS NOTE To remove Adapter Kit 219 0618 refer to Kit 219 0618 RA 55 Connector Adapter Kit Instruction Sheet see PAR 1 1 for downlo...

Page 30: ......

Page 31: ...ST 488 27HT Controller see PAR 1 1 Table 3 1 lists the catastrophic status messages along with the related MST MHT Power Module condi tion 3 1 2 TIMING REQUIREMENTS FOR A VALID STATUS After sending a...

Page 32: ...n or equal to the critical value indicated above will result in automatic return to normal operation 3 2 2 CURRENT MODE In this mode the Power Module is programmed to behave as a current source The us...

Page 33: ...Power Modules is limited to a maximum value which may in some cases be inadequate to fully discharge all external load capacitance To ensure dry relay switching for all output conditions the user mus...

Page 34: ...tage range GL Io VMAX For an ideal current source a no load condition is then defined as infinite conductance zero impedance since this is the only load condition at which the delivered power is zero...

Page 35: ...true if modules are disabled sequentially 3 6 SERIES OPERATION MST MHT Power Modules are designed to allow series operation to achieve higher output volt age if desired Series operation requires deta...

Page 36: ...unt equal to 10 of the Power Module s rated voltage the circuit initiates a fault shutdown procedure as described in PAR 3 7a The tolerance of the fixed overvoltage hardware trigger is the minimum val...

Page 37: ...OUTPUT FAULT indicator to determine recovery action If the indicator is on refer to PAR 3 7 1 for recovery If the indicator is off send RST to recover The open sense power wire protection circuitry ca...

Page 38: ...d in Table 1 1 IMAX is the maxi mum output current of the unit as listed in Table 1 1 for 45 C 3 9 1 EQUIPMENT REQUIRED Calibration of MST MHT Series Power Modules requires the following equipment Hos...

Page 39: ...MST MHT SERIES 071320 3 9 FIGURE 3 1 CALIBRATION TEST SET UP O2 S2 CS GND S1 O1...

Page 40: ...arison amplifier to be zero for a pro grammed output voltage of zero 1 Configure DC OUTPUT connector as shown in Figure 3 1 and open S2 2 With the load disconnected issue commands from the host comput...

Page 41: ...ge Mode program current limit to IMAX output voltage to EMAX and enable the output 2 Verify VOLTAGE MODE and OUTPUT ENABLED indicators are on 3 Connect the voltmeter to DC output connector see Figure...

Page 42: ...Current Mode with output disabled to avoid drift due to temperature fluctuations 2 Enable the output and verify that CURRENT MODE and OUTPUT ENABLED indicators are on 3 Record the output current as m...

Reviews: