6.3.
Calibration of the temperature / humidity sensor
For the MultiSensor-RF / -LAN and -LAN-RF devices, it may be necessary to calibrate the combination sensor
for temperature and humidity once after installation and commissioning.
For this, the temperature must be determined in the immediate vicinity of the MultiSensor (for example with an
infrared thermometer). The difference between the two measured temperatures (meter and MultiSensor) is then
entered as an offset in full degrees in the corresponding field in the sensor configuration.
The correction also has a direct influence on the determined air humidity.
6.4.
Kentix system port on MultiSensor-RF / -LAN / -LAN-RF
The Kentix system socket of the MultiSensor can be used to install system components, such as leakage
sensors, door contacts, sirens or external alarms can be connected of UPS or air conditioners. At the
MultiSensor-RF the system jack is also required for the power supply of the sensor.
Two adapters are available for connecting external devices or external alarms with inputs or outputs:
1) Power-Adapter KIO 1: power supply, 2 digital inputs
2) Power-Adapter KIO 3: power supply, 2 digital inputs and 2 relay outputs
6.5.
MultiSensor-RF
The MultiSensor RF is configured via the AlarmManager. Perform of updates is not possible or required.
6.5.1.
MultiSensor-RF teach-in
1. To add a MultiSensor RF to the AlarmManager configuration, in the alarm zone header area, select "+" in the
dashboard and then select "MultiSensor (Radio)".
2. Press the learn button for 3 seconds, which you can access via the recess on the back of the housing.
3. The sensor should be detected within 15-20 seconds. Subsequently, the configuration mask for the sensor is
opened directly. The teach-in process is completed.
4. Make the individual settings for configuring the sensor and then save the settings.
Page
(07-2018, subject to change)
kentix.com
28
Mu
lti
Se
n
so
rs
Sm
a
rt
Mo
n
ito
ri
n
g
NOTICE!
Depending on the orientation of the MultiSensor (for example, wall mounting, test mode with lateral position or cover
upwards) and the conditions (air conditioning) in the room, a correction by several degrees may be necessary.