2.3  Connection to the mains supply

FastMig power sources are delivered equipped with 5 m mains cable without plug.
If local electricity regulations of operating country are stating otherwise, the mains cable 

should be replaced in conformity with the local regulations.
Connection of the mains cable, mounting and change of the plug should only be carried out 

by a competent electrician.
Remove the machine’s right side plate to enable the mounting of a mains cable.
M 420MV power source can be connected to the mains supply of 220...230 V 3~ or 380...440 V 

3~ .
If changing the mains cable take into consideration the following:
The cable is entered into the machine through the inlet ring on the rear panel of the machine 

and fastened with a cable clamp (05). The phase conductors of the cable are coupled to 

connectors L1, L2 and L3. The earth protection coloured green-yellow is coupled to connector.

NOTE!  

If you are using 5-lead cable, do not connect neutral conductor.

Sizes of the mains cables and fuse ratings for the machine at 100 % duty cycle are specified in 

the table below:

Rated voltage

Fuses, slow-blow

Connection cable *) mm²

380...440 V 3~

35 A

H07RN-F 4G10 (10 mm²) 

220...230 V 3~

50 A

H07RN-F 4G10 (10 mm²)

*) In cables of S type there is a protective grounding conductor coloured green-yellow.

2.4  Welding and earth return cables

Recommended copper cables with cross-sectional area are as follows:
FastMig M 420MV 

70 ... 95 mm²

In enclosed table are shown typical load capacities of rubber insulated copper cables, when 

ambient temperature is 25º C and lead temperature is 85º C.

Cable

Duty cycle ED

Voltage loss / 10 m

100 %

60 %

30 %

50 mm²

285 A

370 A

520 A

0,35 V / 100 A

70 mm²

355 A

460 A

650 A

0,25 V / 100 A

95 mm²

430 A

560 A

790 A

0,18 V / 100 A

Do not overload welding cables due to voltage losses and heating.

NOTE 

! Always check the serviceability of the earth return cable and clamp. Ensure the metal 

surface to which the cable is connected is clean from metal oxide or paint. Check the connector to 

the power source is fastened correctly.

Summary of Contents for M 420MV FastMig

Page 1: ...FastMig M 420MV Operating manual Brugsanvisning Manual de instrucciones Manual de utiliza o EN ES PT NO...

Page 2: ......

Page 3: ...OPERATING MANUAL English...

Page 4: ...achine 6 2 2 Distribution network 6 2 3 Connection to the mains supply 7 2 4 Welding and earth return cables 7 3 Operation controls 8 3 1 Main switch I O 8 3 2 Pilot lamps 8 3 3 Operation of cooling f...

Page 5: ...more information on Kemppi products contact Kemppi Oy consult an authorised Kemppi dealer or visit the Kemppi web site at www kemppi com The specifications presented in this manual are subject to cha...

Page 6: ...Warning lamp for thermal protection 4 Main switch 5 Welding connection 6 Earth connection 7 Control cable connection 8 Inlet of mains cable 1 3 Accessories 1 3 1 Remote control devices R10 1 1 Contro...

Page 7: ...s are correctly fastened Loose connectors can impair welding performance and damage connectors Liquid cooled system FastMig power source MXF FastCool 10 1 4 8 2 3 9 5 6 7 10 1 MXF wire feed unit 2 Fas...

Page 8: ...e against heavy rain and direct sunshine NOTE The machine should not be operated in the rain as the protection class of the machine IP23S allows for outside preserving and storage only NOTE Never aim...

Page 9: ...OTE If you are using 5 lead cable do not connect neutral conductor Sizes of the mains cables and fuse ratings for the machine at 100 duty cycle are specified in the table below Rated voltage Fuses slo...

Page 10: ...will continue to run and cool the machine down and when the lamp is off the machine is ready to weld 3 3 Operation of cooling fan In FastMig power sources there are two simultaneously operating fans...

Page 11: ...t and wait about 2 minutes capacitor charge before removing the cover plate Check at least every half year Electric connectors of the machine clean any oxidized parts and tighten loose connections NOT...

Page 12: ...The machine is designed to withstand 3 x 440 V voltage continuously Ensure that voltage is kept within this permissible limit especially when the mains supply is provided by a combustion engine gener...

Page 13: ...MXF 63 To be used with MR panels 6152300 Panels for wire feeders FastMig MR 200 6136100 FastMig MR 300 6136200 FastMig MS 200 6136300 FastMig MS 300 6136400 Accessories Return current cable 5 m 50 mm...

Page 14: ...V 44V Open circuit voltage MMA U0 48 53V Uav 50V U0 48 53V Uav 50V MIG MAG U0 60 65V U0 53 58V Idle power 25W 25W Efficiency at max current 87 87 Power factor at max current 0 85 0 82 Operating temper...

Page 15: ......

Page 16: ...5428 LANGG NS DEUTSCHLAND Tel 49 6 403 7792 0 Telefax 49 6 403 779 79 74 sales de kemppi com KEMPPI SP KA Z O O Ul Borzymowska 32 03 565WARSZAWA POLAND Tel 48 22 7816162 Telefax 48 22 7816505 info pl...

Reviews: