SNA-Series Tankless Heater

 Installation

10/17/2014 

Keltech • 

215-1815 Rev. B; ECN 130011

Electric Installation

3

CAUTION!  Failure to properly ground the unit(s) per the National Electric Code could result in injury or death.

B

Using a hole punch, cut a hole the proper 
size for conduit connection; large enough 
for the wire size for each heater . The 
connectors need to be rated NEMA4/4X 
to ensure proper sealing of the enclosure . 
(See Figure 2 for suggested location) .

A

Open enclosure door .

C

Run wires through the appropriate size 
conduit .

D

Connect wires to the system terminal 
block or fused disconnect inside the 
enclosure .  

E

Connect the ground wire to the stud 
provided with the “Ground” label beneath it .  

Any option that requires field wiring must 
be done with 600V cable per the schematic 
shipped with the heater.

Use a 4-core cable or multi-stranded 
machine tool wire from an approved 
isolating 3-pole switch or circuit breaker. 
Make sure the electrical cable is the 
correct size to carry 100% of the full load 
current. See Table 1 for proper wire sizes. 

IMPORTANT!  All Keltech heaters must be fused in accordance with National Electric Code for the full 

load amperage listed on the nameplate rating for each heater.

CAUTION!  To avoid damage to the electronics or internal wiring, do not perform any brazing or sweat 

soldering inside the enclosure.

ELECTRICAL SPECIFICATIONS FOR HEATER (PHASE 3)

Model

Voltage

Amps

kWatts

Min Wire 

Size

SNA-363/600D

600

35

36

8 AWG*

SNA-543/600D

600

52

54

6 AWG*

SNA-633/600D

600

61

63

4 AWG*

SNA-723/600D

600

69

72

4 AWG*

SNA-1083/600D

600

104

108

2 AWG*

SNA-1263/600D

600

121

126

1 AWG*

SNA-1443/600D

600

139

144

1/0 AWG*

SNA-363/480D

480

43

36

6 AWG*

SNA-543/480D

480

65

54

4 AWG*

SNA-633/480D

480

76

63

4 AWG*

SNA-723/480D

480

87

72

3 AWG*

SNA-1083/480D

480

130

108

1 AWG*

SNA-1263/480D

480

152

126

1/0 AWG*

SNA-1443/480D

480

174

144

2/0 AWG*

SNA-363/415D

415

38

27

8 AWG*

SNA-543/415D

415

56

40

6 AWG*

SNA-633/415D

415

65

47

4 AWG*

SNA-723/415D

415

75

54

4 AWG*

SNA-1083/415D

415

113

81

2 AWG*

SNA-1263/415D

415

131

94

1 AWG*

SNA-1443/415D

415

150

108

1/0 AWG*

SNA-363/400D

400

36

25

8 AWG*

SNA-543/400D

400

53

37

6 AWG*

SNA-633/400D

400

64

44

4 AWG*

SNA-723/400D

400

72

50

4 AWG*

SNA-1083/400D

400

108

75

2 AWG*

SNA-1263/400D

400

126

87

1 AWG*

SNA-1443/400D

400

144

100

1/0 AWG*

SNA-363/380D

380

35

23

8 AWG*

SNA-543/380D

380

50

33

6 AWG*

SNA-633/380D

380

59

39

6 AWG*

SNA-723/380D

380

68

45

4 AWG*

SNA-1083/380D

380

103

68

2 AWG*

SNA-1263/380D

380

120

79

1 AWG*

SNA-1443/380D

380

137

90

1/0 AWG*

TABLE 1

* Based on the NEC Table 310 .15 for 75°C insulated wire @ 30°C Ambient

Summary of Contents for SNA-36

Page 1: ...ptions 11 12 Maintenance 12 Troubleshooting 12 13 Special Installation Operating Instructions 14 17 IMPORTANT Read this entire installation manual to ensure proper installation When finished with the...

Page 2: ...ntended service Frequency of cleaning and inspection depends upon local water conditions For heaters with adjustable output temperatures check and adjust as needed at initial installation and on a qua...

Page 3: ...eaters from Rain or other falling precipitation via tarp or other waterproof media Runoff and accumulation of groundwater from any source that may exceed 1 inch NOTE For heaters with ENHT freeze prote...

Page 4: ...mperature relief valve on hot water outlet immediately following the union NOTE Valve must empty into a drain See Figure 2 B Remove air by re installing drain plugs and open inlet supply valve to appl...

Page 5: ...stem or at any drop to eliminate trapped air Components Needed 5 Union 1 1 4 Shutoff Valve Pressure and Temperature Relief Valve 150 psi Y Strainer 100 mesh or Inline Filter 150 microns 2 Gate or Ball...

Page 6: ...rating for each heater CAUTION To avoid damage to the electronics or internal wiring do not perform any brazing or sweat soldering inside the enclosure ELECTRICAL SPECIFICATIONS FOR HEATER PHASE 3 Mo...

Page 7: ...ief valve on outlet if required by local or national plumbing codes If the hot water process is not at the highest point in the plumbing loop then an automatic air vent valve must be added at the high...

Page 8: ...et shower etc then flush the system for 5 minutes to ensure all air is purged from the system CAUTION Failure to bleed air properly will damage elements and cause heater malfunction Be sure that plumb...

Page 9: ...me page Advance Key Advances through parameter prompts Auto Man Off C r71 Turns Control Loop On Manual Off Disabled on SNA Models XX X h Pr1 Heater Power Disabled on SNA Models no AUt1 Autotune Contac...

Page 10: ...e of approximately 10 psi For example if the high limit pressure is 40 psi adjust the low limit pressure to 30 psi with the pressure switch located on the supply pump Heater will not energize heating...

Page 11: ...fault After turning on water then power test ground fault 1 Press GF Test button 2 Watch for ground fault light to illuminate and Bank Ready light s to shut off The Ground Fault system is active and...

Page 12: ...he heat exchangers may trip at temperatures below 32 F on heaters equipped with ENHT or ENHT30 Manual resets are set to trip at 100 F 38 C Heat trace installed on connected piping can heat water to te...

Page 13: ...dicated Bank 1 2 on the front bezel Bank 1 on the FLCB Bank 3 4 on the front bezel Bank 2 on the FLCB If the light is off and there is power on Check if water temperature is greater than 175 F Decreas...

Page 14: ...nlet fitting here FIGURE 6 EXP2 EXP2LC Installation Notes 1 Any tubing conduit or fittings connected to the Pressurized Enclosure PE must conform to local codes for flammability ratings 2 All egress i...

Page 15: ...ure and the protective gas supply The alarm actuator shall be mechanical pneumatic or electrical Electrical alarms and electrical alarm actuators shall be approved for the location in which they are i...

Page 16: ...roved the interior of the PE is gas free and checked that the Pressurized indicator is green Commissioning Test Commissioning Leakage Compensation LC and Continuous Flow High Purge Keltech Options EXP...

Page 17: ...larms function correctly Check the Relief Valve and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor Check the condition of the air supply filter element Clean or...